TABLE OF USER MENU PARAMETERS (IDPLUS 902/961)
PAR. DESCRIPTION
RANGE
APP1 APP2 APP3 APP4 M.U.
SEt Temperature control SEtpoint
LSE ... HSE
0,0
0,0
0,0
-2,0
°C/°F
diF Compressor relay activation differential
0,1 ... 30,0
2,0
2,0
2,0
0,1
°C/°F
HSE Maximum value that can be assigned to the Setpoint
LSE ... 302
99,0
140
140
5,0
°C/°F
LSE Minimum value that can be assigned to the Setpoint
-58.0 ... HSE
-50,0 -55,0 -55,0 -10,0 °C/°F
dit
Interval between the start of two consecutive defrost cycles
0 ... 250
6
8
hours
dEt Defrost timeout
1 ... 250
30
30
min
HAL Maximum temperature alarm
LAL ... 150
50,0
150
150
50,0 °C/°F
LAL Minimum temperature alarm
-50.0 ... HAL
-50,0 -50,0 -50,0 -50,0 °C/°F
SA3 Probe 3 alarm Setpoint
-50.0 ... 150
70,0 °C/°F
LOC Basic commands modification lock
n/y
n
n
n
n
flag
PS1 PAssword 1 for access to QUICK menu parameters
0 ... 250
0
0
0
0
num
CA1 Calibration1. Value to be added to the value read by probe 1
-12,0 ... 12,0
0,0
0,0
0,0
0,0
°C/°F
CA3 Calibration3. Value to be added to the value read by probe 3
-12,0 ... 12,0
0,0
°C/°F
ddL Display mode during defrost
0/1/2
0
0
num
Ldd Display lock disabling timeout. 0 = function disabled
0 ... 255
30
30
min
H43 Probe 3
present. n = not present; y = present
n/y
y
flag
rEL firmware rELease. Reserved: read-only parameter
/
/
/
/
/
/
tAb tAble of parameters. Reserved: read-only parameter
/
/
/
/
/
/
Notes
: ** The USER menu parameters also include “
PA2
”, which can be used to access the Installer menu
*** For the complete list of parameters, see: APPENDIX A:
Table of
Installer
menu parameters