Classification:
operation (not safety) device for incorporation
Mounting:
panel mounting with 71x29 mm (+0.2/-0.1 mm) drilling template
Type of action:
1.B
Pollution class:
2
Material class:
IIIa
Overvoltage category:
II
Rated impulse voltage:
2500V
Temperature:
Use: -5 … +55°C - Storage: -30 … +85 °C
Power supply:
12V
a
/
c
(
±
10%) 50/60 Hz or 230V
a
(
±
10%) 50/60 Hz
Consumption:
4.5W max
Digital outputs (relay):
refer to the label on the device
Fire resistance category: D
Software class:
A
NOTE: check the power supply specified on the instrument label; contact our Sales Office for power supply
and relay ratings.
TECHNICAL DATA (EN 60730-2-9)
FURTHER INFORMATION
Input Characteristics
Display range:
NTC
: -50.0°C ... +110°C;
PTC
: -55.0°C ... +140°C;
PT1000
: -55.0°C ... +150°C
(on display with 3 sign)
Accuracy:
NTC, PTC, PT1000
(-55,0°C...+70°C)
:
Better than 0.5% of full scale +1 digit
PT1000
(+70,0°C...+150°C):
Better than 0.6% of full scale +1 digit
Resolution:
0.1 °C
Buzzer:
YES (depending on model)
Analogue inputs:
IDPlus 902/961
: 1 NTC (default)/PTC/PT1000 (can be selected using parameter
H00
)
IDPlus 971/974
: 2 NTC (default)/PTC/PT1000 (can be selected using parameter
H00
)
Digital inputs:
IDPlus 902/961
: 1 voltage-free digital input;
IDPlus 971/974
: 2 voltage-free digital inputs
N.B.
: - D.I.1 can also be configured as a probe input (
H11
=0 and
H43
=y)
- D.I.2, if activated, should be connected to terminals 1-2 of the TTL (
IDPlus 971/974
)