PAR. DESCRIPTION
MODEL
RANGE
VALUE M.U. LEVEL
SAO
Alarm exclusion time until the Setpoint is reached.
0
= disabled. If
SAO
>0, an alarm will be generated if the Setpoint is not
reached after the time
SAO
(in hours).
ALL
0...10
0
hours
Inst
tAO
Delay preceding indication of temperature alarm.
ALL
0...250
0
min
Inst
AOP
Alarm output polarity.
nC
(0) = alarm active and output disabled
nO
(1) = alarm active and output enabled
ALL
nC/nO
nC
flag
Inst
tP
Enable all keys to acknowledge an alarm.
n
(0) = no;
y
(1) = yes.
ALL
n/y
y
flag
Inst
COMMUNICATION (folder ‘Add’)
PtS
Selection of communication protocol.
t
= Televis;
d
= Modbus.
ALL
t/d
t
flag
Inst
dEA
Index of the device within the family (valid values from 0 to 14).
ALL
0...14
0
num
Inst
FAA
Device family (valid values from 0 to 14).
ALL
0...14
0
num
Inst
Adr
Modbus protocol controller address.
ALL
1...255
1
num
Inst
bAU
Baudrate selection.
48
(0) = 4800;
96
(1) = 9600;
192
(2) = 19200;
384
(3) = 38400.
ALL
48/96/
192/384
96
num
Inst
Pty
Modbus parity bit.
n
(0) = none;
E
(1) = even;
o
(2) = odd.
ALL
n/E/o
E
num
Inst
StP
Modbus stop bit.
1b
(0) = 1 bit;
2b
(1) = 2 bit.
ALL
1b/2b
1b
flag
Inst
DISPLAY (folder ‘diS’)
LOC
LOCk. Setpoint edit lock. The parameter programming menu can still be
accessed, and the settings changed, which means also that the status of this
parameter can be changed so as to unlock the keypad.
n
(0)= no;
y
(1) = yes.
ALL
n/y
n
flag User/Inst
PS1
Password 1. When enabled (
PS1 ≠ 0
) it is the password to the ‘
User
’
parameters (User).
ALL
0...250
0
num User/Inst
PS2
Password 2. When enabled (
PS2 ≠ 0
) it is the password to the ‘
Installer
’
parameters (Inst).
ALL
0...250
15
num
Inst
ndt
Display values with decimal point.
n
(0) = no (integers only);
y
(1) = yes (displayed with decimal point);
int
(2) = integer.
ALL
n/y/int
n
num User/Inst