PARAMETERS TABLE
PAR. DESCRIPTION
MODEL
RANGE
VALUE M.U. LEVEL
SP1
Temperature control setpoint
SP1
.
The SEtpoint is visible from the
machine status menu and not from the programming menu.
NTC/PTC
LS1...HS1
0.0
°C/°F
PT100-Tc
0.0
°C/°F
V/I
0
num
SP2
Temperature control setpoint
SP2
.
The SEtpoint is visible from the
machine status menu and not from the programming menu.
NTC/PTC
LS2...HS2
0.0
°C/°F
PT100-Tc
0.0
°C/°F
V/I
0
num
CONTROLLER 1 (folder ‘rE1’)
HC1
This sets the controller 1 operating mode.
H
(0) = Hot;
C
(1) = Cold.
ALL
H/C
H
flag
Inst
OS1
Temperature value to be added to
SP1
if reduced set enabled
NTC/PTC
-30.0...30.0
0.0
°C/°F
Inst
PT100-Tc
-30.0...30.0
0.0
°C/°F
V/I
-30...30
0
num
db1
Operating band 1.
(
See ‘ON/OFF regulation diagram’
)
NTC/PTC
0.0...30.0
1.0
°C/°F
Inst
PT100-Tc
0.0...30.0
1.0
°C/°F
V/I
0...30
1
num
dF1
OUT1
activation differential.
The utility stops on reaching the
SP1
value (as indicated by control probe) and
restarts at a temperature value equal to
T=SP1+dF1
relative to
HC1
.
NTC/PTC
0.0...30.0
1.0
°C/°F
User/Inst
PT100-Tc
0.0...30.0
1.0
°C/°F
V/I
0...30
1
num
HS1
Maximum value assignable to setpoint SP1.
NTC/PTC
LS1...HdL
140.0
°C/°F
User/Inst
PT100-Tc
1350
°C/°F
V/I
199
num
LS1
Minimum value assignable to setpoint SP1.
NTC/PTC
LdL...HS1
-50.0
°C/°F
User/Inst
PT100-Tc
-199.9
°C/°F
V/I
-199
num
HA1
Maximum temperature alarm on OUT1.
(
See ‘Max/Min temperature alarms’
)
NTC/PTC
LA1...150.0
140.0
°C/°F
User/Inst
PT100-Tc
LA1...1999
1350
°C/°F
V/I
LA1...150
150
num