PAR. DESCRIPTION
MODEL
RANGE
VALUE M.U. LEVEL
dF2
OUT2
activation differential. The utility stops on reaching the
SP2
value
(as indicated by control probe) and restarts at a temperature value equal to
T=SP2+dF2
relative to
HC2
.
NTC/PTC
0.0...30.0
1.0
°C/°F
User/Inst
PT100-Tc
0.0...30.0
1.0
°C/°F
V/I
0...30
1
num
HS2
Maximum value assignable to setpoint SP2.
NTC/PTC
LS2...HdL
140.0
°C/°F
User/Inst
PT100-Tc
1350
°C/°F
V/I
199
num
LS2
Minimum value assignable to setpoint SP2.
NTC/PTC
LdL...HS2
-50.0
°C/°F
User/Inst
PT100-Tc
-199.9
°C/°F
V/I
-199
num
HA2
Maximum temperature alarm on OUT2.
(
See ‘Max/Min temperature alarms’
)
NTC/PTC
LA2...150.0
140.0
°C/°F
User/Inst
PT100-Tc
LA2...1999
1350
°C/°F
V/I
LA2...150
150
num
LA2
Minimum temperature alarm on OUT2.
(
See ‘Max/Min temperature alarms’
)
NTC/PTC
-150.0...HA2
-50.0
°C/°F
User/Inst
PT100-Tc
-328...HA2
-199.9
°C/°F
V/I
-150...HA2
-150
num
dn2
Switch-on delay. The indicated time must elapse between the request for
activation of the controller 2 relay and switch-on.
0
= not active.
ALL
0...250
0
min
Inst
dO2
Delay time after switching off. The indicated time must elapse between
deactivation of the controller 2 relay and the next switch-on.
0
= not active.
ALL
0...250
0
min
Inst
di2
Delay between switch-ons. The indicated time must elapse between two
consecutive switch-ons of regulator 2.
0
= not active.
ALL
0...250
0
min
Inst
dE2
Switch-off delay. The indicated time must elapse between the request for
deactivation of the controller 2 relay and switch-off.
0
= not active.
ALL
0...250
0
min
Inst
On2
Controller 2 switch-on time in the event of faulty probe.
if
On2
=1 and
OF2
=0, the controller remains on;
if
On2
=1 and
OF2
>0, the controller operates in Duty Cycle mode.
ALL
0...250
0
min
Inst