background image

IC\.912 LX Pt100 °R

7/8

DIAGNOSTICS

The alarm condition is always signalled by
the buzzer (if present) and by the led of

the alarm icon 
The alarm signal produced by: 
• a regulator probe that measures a value
outside probe’s range 
• a faulty regulator probe
is shown as E1 on the instrument display

PLEASE NOTE:

In case of wrong connec-

tion of the 3rd wire (Pt100 sensor) in
“AL” folder it will appear the label “Pt3”.
For  few seconds the display will shows a
uncorrect temperature.
When the sensor detects an error condi-
tion: 
• the code E1 is displayed 
• the regulator is activated as indicated by
the "On1" and "OF1" parameters if pro-
grammed for the duty cycle or:

MAXIMUM AND MINIMUM TEMPERA-
TURE ALARM

In case of alarm condition, if alarm exclu-
sion times are not in progress (see, alarm
exclusion parameters), the fixed alarm
icon is turned on and  the relay config-
ured as an alarm is activated. This kind of
alarm does not affect the regulation in
progress. Alarms are considered as
absolute (Abs, default) values or as values
related to the Setpoint (rEL, the distance
from the Setpoint itself) and based on the
Att parameter. In this case (Att=rEL), the
HA1 parameter must be set to positive
values and the LA1 parameter to negative
values.
This alarm condition can be viewed in the
folder “AL” with the labels “AH1-AL1”.

EXTERNAL ALARM

The device includes the possibility to con-
trol an external alarm, from a digital input.
If the digital input is active, the alarm con-
trol is activated, if programmed, and stays
until the next time the digital input is
deactivated. The alarm is signaled by turn-
ing on the fixed alarm icon, by activating
the relay configured as alarm, and by
deactivating the other regulators (if speci-
fied by the “H11=9” parameter). 
This alarm condition can be viewed in the
“AL” folder with the label “EA”. The relay
can be silenced; even if alarm icon starts
blinking, controls stay locked until the
next time the digital input is deactivated. 

DIAGNOSTICS

DISPLAY

E1 

FAULT

Faulty probe 1 (thermostat control) 

Table of faulty probes

DISPLAY

AH1**

AL1**

EA 
Opd
Press any button to silence the alarm. The LED will
start to blink.

ALARM

High temperature alarm (referring to
probe Pb1/Pb2 based on par. H04) 
Low temperature alarm (referring to
probe Pb1/Pb2 based on par. H04) 
External alarm 
Door Open Alarm

Alarm table

Minimum temperature alarm

Maximum temperature alarm

LAL

AFd

HAL

AFd

1

set+ LAL

AFd

Off

set+HAL

AFd

set

2

Temperature lower than or equal to LA1(2) (LA1(2) with sign)

Temperature lower than or equal to set point +LA1(2) positive only)

Temperature greater than or equal to set point +HA1(2) (HA1(2) positive only)

Temperature greater than or equal to HA1(2) (HA1(2) with sign)

Maximum temperature alarm
back swing

Minimum temperature alarm
back swing

Temperature greater than or equal to LA1(2)+AFd

Temperature greater than or equal to set point + LA1(2) + AFd
set point -|LA1(2)|+AFd

Temperature lower than or equal to set point+HAL-AFd

Temperature lower than or equal to HA1(2)-AFd

Temperature expressed as an absolute value (par “Att0)
Abs(olute)

Temperature expressed in relation to set point
(par “Att”=0) reL(ative)

if Att=reL(ative) LA

1(2)

must be negative: therefore 

set point+LAL<set point because set point+(-|LA

1(2)

|)=set-|LA

1(2)

|

ALARM DIAGRAM HIGH AND LOW TEMPERATURE

OF1

Off

On

OUT

On1

On1

An error condition in probe 1
(regulation) leads to:
• E1 code appears on display
• activation of controller as
indicated by the “On1” and
“OF1” parameters if pro-
grammed for the duty cycle

Ont


0
>0
>0

OFt

0
>0 
0
>0

Compressor output

OFF 
OFF 
ON 
dc

DUTY CYCLE DIAGRAM

On1 OF1 parameters programmed for
Duty Cycle

Содержание IC 912 LX Pt100 R

Страница 1: ...probe errors the AL label appears By using the UP and DOWN buttons you can scroll through the other folders in the menu the folders are indicated below in the order they appear SP1 Set point 1 setting folder or AL alarm folder if alarms present with exception of faulty probes probe errors Pb1 probe 1 value folder IC 912 LX Pt100 R electronic controller with single output and regulation in Réaumur ...

Страница 2: ...ing parameters to the instrument NOTE UPLOAD instrument Copy Card DOWNLOAD Copy Card instru ment The operations are performed by access ing the folder identified by the FPr label and selecting the UL dL or Fr commands The operation is confirmed by pressing the set button If the oper ation is successful a y is displayed whereas if it is unsuccessful an n will be displayed Download from reset Connec...

Страница 3: ...tton and the value 0 will appear enter the password using the UP DOWN buttons and press the set button again This allows you to access the level 2 parameters The first folder that appears is CP NOTE At this level the folders will only display all the level 2 parame ters Therefore level 1 parameters will only be visible if you quit the Programming Menu and repeat proce dure 1 NOTE It is strongly re...

Страница 4: ... label on the instrument Buzzer output only on models with Buzzer Measuring range from 150 to 1350 Accuracy 0 5 for all scale 1 digit 0 2 from 120 to 240 C Resolution 0 1 R within 199 9 C 1 R over Consumption model 230V 3 VA max model 12 24V 1 5 VA max Power supply 12 24 Va c 10 or 230Va 10 50 60 Hz Warning check the power supply specified on the instrument label for relay and power supply capacit...

Страница 5: ...ART function ALARMS folder with AL label Alarm type Parameter HA1 and LA1 modes as temperature absolute values or as differential compared to the Setpoint 0 absolute value 1 relative value Alarm Fan differential Alarm differential Power on Alarm Override Alarm exclusion time after instrument switch on after a power failure Setpoint Alarm Override Exclusion alarm time until Setpoint is reached 0 di...

Страница 6: ...from power on WARNING If set 0 it is not active if set 0 output will not be activated before this time Configuring digital inputs 0 disabled 1 SOFT START 2 Offset Setpoint 3 outputs stopped 4 not used 5 auxiliary output 6 stand by 7 maintenance requested 8 external alarm 9 external alarm stop regulators Polarity and Priority Digital Input no normally open nc normally closed noP normally open with ...

Страница 7: ...ulators if speci fied by the H11 9 parameter This alarm condition can be viewed in the AL folder with the label EA The relay can be silenced even if alarm icon starts blinking controls stay locked until the next time the digital input is deactivated DIAGNOSTICS DISPLAY E1 FAULT Faulty probe 1 thermostat control Table of faulty probes DISPLAY AH1 AL1 EA Opd Press any button to silence the alarm The...

Страница 8: ...ustomer Support Email techsuppeliwell invensys com Telephone 39 0437 986300 Climate Controls Europe An Invensys Company 11 2004 eng cod 9IS23094 SP1 SP1 dF1 dF1 Off On HC1 H SP1 dF1 SP1 dF1 Off On HC1 C HC1 Heat Cool Mode SP1 Setpoint 1 dF1 diFferential Relay 1 tripping differential ON OFF REGULATION DIAGRAM RS232 to PC RS485 BusAdapter PCInterface TTL PC with Televis package 230V N L 230V N L The...

Отзывы: