AUX (Auxiliary Regulator)

The Digital Input can be set as “auxiliary”
(parameter H11=5): in this case define the
regulator output 1as aux (auxiliary)
through H21 parameters.
This function permits to activate the relay
if it was not excited or to leave it excited
on the other side. The status will be
stored, to ensure a correct functioning, in
case of black-out, except when you set
parameter H11=5 (aux); in this case the
relay status is the same as the Digital Input
status.
Through parameter H13 you can define
priorities/polarity between atctivation
through key, relay and Digital Input.

NOTE: The meaning of the Digital Input
(D.I.) should remains the same: e.g.
enabling relay from D.I. and disabling it
from key, if you reset the D.I. the relay
doesn’t change its status  because it is
disabled from key.

INSTALLATION

The instrument is designed for panel
mounting. Make a hole of 29x71 mm,
insert the instrument and fix it using the
brackets provided. Do not mount the
instrument in humid and/or dirty places; it
is suitable for use in ordinary polluted
places. Ventilate the place in proximity to
the instrument colling slits.

ELECTRICAL 
WIRING

Attention! Never work on electrical
connections when the machine is
switched on.

The instrument is equipped with screw ter-
minal boards for connection of electrical
cables with a diameter of 2.5 mm

2

(one

conductor only per terminal for power
connections).
For the capacity of the terminals, see the
label on the instrument.
The relay contacts are voltage free. Do not
exceed the maximum current allowed; in
case of higher loads, use an appropriate
contactor. Make sure the power supply
voltage complies with the one required by
the instrument.
Probe cables, power supply cables and the
TTL serial cables should be distant from
power cables.
In 12V versions  the power supply however
could be cabled  with the probe cables
and the TTL serial cable.
In 230 V versions  the power supply
should be cabled  with the loads.
Probes can be extended using a regular
bipolar cable (note that the extension of
the probes affects the EMC electromagnet-
ic compatibility of the instrument: pay
extreme attention to wiring). 

NOTE: Pay extreme attention to the
probe connection polarity.

TECHNICAL DATA 

Frontal panel protection: IP65.
Casing: plastic body in resin type
PC+ABS UL94 V-0, inspection window in
polycarbonate, buttons in thermoplastic
resin.
Dimensions: frontal panel 74x32 mm,
depth 59 mm (without wirings).
Installation: on panel, with drilling tem-
plate 71x29 mm (+0.2/–0.1 mm).
Use temperature:  –4…44 °R.
Storage temperature.: –24…68 °R.
Use environment humidity: 10…90 % RH
(not condensing).
Storage environment humidity: 10…90% RH
(not condensing).
Viewing range:  -120…640°R, with decimal
point, selectable through parameter ndt
on 3 digit & 

1

/

2

+ mark display.

PLEASE NOTE: viewing is 1/10 °R.

Serial: TTL for connection to Copy Card
and Televis

System

.

Analogue input: one PT100 input.
Digital inputs: 1 voltage-free digital input. 
Digital output: 1 SPDT output on 8(3)A
1/2 hp configurable. (for relay capabilities
see label on the instrument)
Buzzer output: only on models with
Buzzer.
Measuring range: from -150 to 1350.
Accuracy:  
• 0,5% for all scale + 1 digit; 
• 0,2% from -120 to 240°C.
Resolution: 
• 0,1°R within 199,9 °C, 
• 1°R over
Consumption:
• model 230V: 3 VA max.
• model 12/24V: 1,5 VA max.
Power supply: 12/24 V

a

/

c

±10% or 230V

a

±10% 50/60 Hz. 

Warning: check the power supply specified
on the instrument label; for relay and
power supply capacities, contact the Sales
Office).

IC 912 LX Pt100 °R

4/8

PLEASE NOTE: The technical data
included in this document, related to
measurement (range, accuracy, resolu-
tion, etc.) refer to the instrument
itself, and not to its equipment such as,
for example, sensors.
This means, for example, that sensor(s)
error(s) shall be added to the instru-
ment’s one.

CONDITIONS OF USE 
Permitted Use

For safety reasons the instrument must be installed
and used in accordance with the instructions supplied. 
Users must not be able to access parts with dangerous
voltage levels under normal operating conditions. 
The device must be suitably protected from water and
dust according to the specific application and only be
accessible using special tools (except for the front key-
pad). 
The device is ideally suited for household use and/or
similar use in the refrigeration sector and has been
tested with regard to safety in accordance with the
European harmonized reference standards. It is classi-
fied as follows:
• as an automatic electronic control device to be inde-
pendently mounted as regards its construction;
• as a 1 B type operated control device as regards its
automatic operating features;
• as a Class A device as regards the category and
structure of the software. 

Unpermitted use 

The use of the unit for applications other than those
described is forbidden. 
It should be noted that the relay contacts supplied
with the device are functional and therefore exposed
to potential faults. 
Any protection devices required to comply with prod-
uct requirements or dictated by common sense due to
obvious safety reasons should be installed externally.

RESPONSIBILITY AND RESIDUAL RISKS

Eliwell & Controlli s.r.l. shall not be liable for any dam-
ages deriving from:
- installation/use other than that prescribed and, in par-
ticular, which does not comply with the safety standards
specified in the regulations and/or those given herein;
- use on equipment that does not guarantee adequate
protection against electric shock, water or dust when
assembled.
- use on equipment that allows dangerous parts to be
accessed without the use of tools;
- tampering with and/or alteration of the product;
- use on equipment that does not comply with the stan-
dards and regulations in force.

DISCLAIMER

This document is the exclusive property of Eliwell &
Controlli s.r.l. and cannot be reproduced and circulat-
ed unless expressly authorized by Eliwell & Controlli
s.r.l.. 
Although Eliwell & Controlli s.r.l. has taken all possible
measures to guarantee the accuracy of this document,
it declines any responsibility for any damage arising
out of its use. 
The same applies to any person or company involved
in preparing and writing this manual. Eliwell & Controlli
s.r.l. reserves the right to make any changes or
improvements without prior notice and at any time. 

Содержание IC 912 LX Pt100 R

Страница 1: ...probe errors the AL label appears By using the UP and DOWN buttons you can scroll through the other folders in the menu the folders are indicated below in the order they appear SP1 Set point 1 setting folder or AL alarm folder if alarms present with exception of faulty probes probe errors Pb1 probe 1 value folder IC 912 LX Pt100 R electronic controller with single output and regulation in Réaumur ...

Страница 2: ...ing parameters to the instrument NOTE UPLOAD instrument Copy Card DOWNLOAD Copy Card instru ment The operations are performed by access ing the folder identified by the FPr label and selecting the UL dL or Fr commands The operation is confirmed by pressing the set button If the oper ation is successful a y is displayed whereas if it is unsuccessful an n will be displayed Download from reset Connec...

Страница 3: ...tton and the value 0 will appear enter the password using the UP DOWN buttons and press the set button again This allows you to access the level 2 parameters The first folder that appears is CP NOTE At this level the folders will only display all the level 2 parame ters Therefore level 1 parameters will only be visible if you quit the Programming Menu and repeat proce dure 1 NOTE It is strongly re...

Страница 4: ... label on the instrument Buzzer output only on models with Buzzer Measuring range from 150 to 1350 Accuracy 0 5 for all scale 1 digit 0 2 from 120 to 240 C Resolution 0 1 R within 199 9 C 1 R over Consumption model 230V 3 VA max model 12 24V 1 5 VA max Power supply 12 24 Va c 10 or 230Va 10 50 60 Hz Warning check the power supply specified on the instrument label for relay and power supply capacit...

Страница 5: ...ART function ALARMS folder with AL label Alarm type Parameter HA1 and LA1 modes as temperature absolute values or as differential compared to the Setpoint 0 absolute value 1 relative value Alarm Fan differential Alarm differential Power on Alarm Override Alarm exclusion time after instrument switch on after a power failure Setpoint Alarm Override Exclusion alarm time until Setpoint is reached 0 di...

Страница 6: ...from power on WARNING If set 0 it is not active if set 0 output will not be activated before this time Configuring digital inputs 0 disabled 1 SOFT START 2 Offset Setpoint 3 outputs stopped 4 not used 5 auxiliary output 6 stand by 7 maintenance requested 8 external alarm 9 external alarm stop regulators Polarity and Priority Digital Input no normally open nc normally closed noP normally open with ...

Страница 7: ...ulators if speci fied by the H11 9 parameter This alarm condition can be viewed in the AL folder with the label EA The relay can be silenced even if alarm icon starts blinking controls stay locked until the next time the digital input is deactivated DIAGNOSTICS DISPLAY E1 FAULT Faulty probe 1 thermostat control Table of faulty probes DISPLAY AH1 AL1 EA Opd Press any button to silence the alarm The...

Страница 8: ...ustomer Support Email techsuppeliwell invensys com Telephone 39 0437 986300 Climate Controls Europe An Invensys Company 11 2004 eng cod 9IS23094 SP1 SP1 dF1 dF1 Off On HC1 H SP1 dF1 SP1 dF1 Off On HC1 C HC1 Heat Cool Mode SP1 Setpoint 1 dF1 diFferential Relay 1 tripping differential ON OFF REGULATION DIAGRAM RS232 to PC RS485 BusAdapter PCInterface TTL PC with Televis package 230V N L 230V N L The...

Отзывы: