PAR.

HC1

OS1
db1
dF1

HS1
LS1
HA1
LA1

dn1

do1

di1

dE1

On1

OF1

dSi

dSt

Unt
SEn

Sdi

Att

AFd
PAO (!)

(8)

SAO

tAO (8)

dEA (!)

FAA (!)

LOC

PA1

PA2****

ndt

CA1

CAI

LdL
HdL

5/8

DESCRIPTION

REGULATOR 1 (folder with “rE1” label)

Heat/Cool Mode. If set to H the generic regulator actuates for hot
operation. If set to C the generic regulator actuates for cold operation

Offset Setpoint 1 

see ON-OFF regulation diagram

Operating Range 2 

see ON-OFF regulation diagram

diFferential. Relay 1 tripping differential. The regulator stops on reach-
ing the Setpoint value (as indicated by the adjustment probe), and
restarts at temperature value equal to the Setpoint 1 plus (o minus
depending on HC1) the value of the differential.  

see ON-OFF regula-

tion diagram

Higher SEt. Maximum possible setpoint 1 value.
Lower SEt. Minimum possible setpoint 1 value. 
Maximum Alarm OUT

See Max/Min. Alarm Diagram

Maximum Alarm OUT 

See Max/Min. Alarm Diagram

REGULATOR 1 PROTECTIVE DEVICE (folder with “rE1” label)

Delay time in activating the regulator relay after switch-on of instru-
ment. 
Delay after switch off. The indicated time must elapse between switch-
off of the regulator relay and the successive switch-on. 
Delay between switch-ons. The indicated time must elapse between
two successive switch-ons of the regulator.
Delay before switch-off. The indicated time must elapse between
switch-off request and the switch-off of  the regulator.

PLEASE NOTE: for parameters dn1, do1, di1, dE1  0= not active

On time (regulator 1). 
Regulator activation time in the event of faulty probe. If set to “1”
with OF1 at “0” the regulator  is always on, while at OF1 >0 it func-
tions always in duty cycle mode. 

see Duty Cycle diagram

OFF time (regulator 1). Regulator in disabled state time in the event of
a faulty probe. If set to “1” with On1 at “0” the regulator is always off,
while at On1 >0 it functions always in duty cycle mode. 

see DC diagr.

SOFT START (folder with label “SFt”)

dynamic Step increment (Step Value). Value (°R) of every incremental
step (dynamic) of the regulation (set)point. 0=disable SOFT START
function.
dynamic Step time (Step Duration). Delay time between two steps 
(dynamic) of the regulation (set)point
U.M (hours, minuts, seconds)
Outputs enabled. Define on which output the function should be
enabled: 0 = function disabled; 1 = OUT 1; 2,3 = not used
Function Threshold re-entry . Define the threshold, over which there is
the automatic re-entry of the SOFT START function

ALARMS (folder with “AL” label)

Alarm type. Parameter “HA1” and “LA1” modes, as temperature
absolute values or as differential compared to the Setpoint. 
0 = absolute value; 1 = relative value. 
Alarm Fan differential. Alarm differential. 
Power-on Alarm Override. Alarm exclusion time after instrument
switch on, after a power failure. 
Setpoint Alarm Override. Exclusion alarm time until Setpoint is
reached. 0 = disabled. If >0, an alarm occours, if setpoint has not been
reached after the time (hours) set by this parameter. 
temperature Alarm Override. Temperature alarm signal delay time. 

COMMUNICATION (folder with “Add” label)

DEA= device number within the family (valid values: from 0 to 14)

FAA= device family (valid values: from 0 to 14)
The value couple FAA and dEA represents the network address of the
device and it is indicated in the following way: "FF.DD" (where FF=FAA
and DD=dEA).

DISPLAY (folder with “diS” label)

(keyboard) LOCk (set and keys). Keyboard locking. However, you can
enter parameter programming
modify them along with the status of this parameter in order to allow
keyboard locking. y = yes; n = no
PAssword 1. When enabled (value other than 0) it constitutes the
access key for level 1 parameters.
PAssword 2. When enabled (value different from 0) it represents the
access key for level 2 parameters. 
number display type. View with decimal point. y = yes; n = no

CAlibration 1.Calibration 1. Positive or negative temperature value
added to the value read by probe 1, 
CAlibration Intervention. Intervention on view offset, thermostat offset
or both. 
0 = modifies the temperature displayed only; 
1 = adds to the temperature used by regulators, not to the tempera-
ture displayed, which stays unchanged; 
2 = adds to the temperature displayed that is also used by regulators. 
Low display Label. Minimum value the instrument is able to display. 
High display Label. Maximum value the instrument is able to display. 

Tab. 1

Parameter Table

DEFAULT*

H/C*

0

1*

0 (n.z. models)*

1*

*
*
*
*

1

0

0

0

0

1

0

0

1
0

0

Abs

2.0

0

0

0

0

0

n

0

0

n

0

2

*
*

RANGE

H/C

-30.0...30.0

0...30.0

0.0...30.0

LS1..HdL
LdL..HS1

LA1…640

-160…HA1

0...250

0...250

0...250

0...250

0...250

0...250

0…25.0

(0…twentyfive.0)

0…250

0/1/2

0/1/2/3

0…30.0

Abs/reL

1.0…50.0

0…10

0…10

0…250

0…14

0…14

n/y

0...250

0...250

n/y

-30.0...30.0

0/1/2

-328.0…HdL

LdL…1999

VALUE**

U.M.

flag

°R
°R
°R

°R
°R
°R
°R

°R

sec

min

min

sec

min

°R

H/m/sec

H/m/sec

num

°R

flag

°R

hours

hours

min

num

num

flag

num

num

flag

°R

°R
°R

LEVEL**

1

2

1
1

1
1
1
1

1

1

1

1

1

1

2

2

2
2

2

2

2

1

1

1

1

1

1

1

2

1

2

2
2

IC 912 LX Pt100 °R

**NOTE: At level 1 the folders will show only level 1 parameters. At level 2 the folders will show only level
2 parameters.

Содержание IC 912 LX Pt100 R

Страница 1: ...probe errors the AL label appears By using the UP and DOWN buttons you can scroll through the other folders in the menu the folders are indicated below in the order they appear SP1 Set point 1 setting folder or AL alarm folder if alarms present with exception of faulty probes probe errors Pb1 probe 1 value folder IC 912 LX Pt100 R electronic controller with single output and regulation in Réaumur ...

Страница 2: ...ing parameters to the instrument NOTE UPLOAD instrument Copy Card DOWNLOAD Copy Card instru ment The operations are performed by access ing the folder identified by the FPr label and selecting the UL dL or Fr commands The operation is confirmed by pressing the set button If the oper ation is successful a y is displayed whereas if it is unsuccessful an n will be displayed Download from reset Connec...

Страница 3: ...tton and the value 0 will appear enter the password using the UP DOWN buttons and press the set button again This allows you to access the level 2 parameters The first folder that appears is CP NOTE At this level the folders will only display all the level 2 parame ters Therefore level 1 parameters will only be visible if you quit the Programming Menu and repeat proce dure 1 NOTE It is strongly re...

Страница 4: ... label on the instrument Buzzer output only on models with Buzzer Measuring range from 150 to 1350 Accuracy 0 5 for all scale 1 digit 0 2 from 120 to 240 C Resolution 0 1 R within 199 9 C 1 R over Consumption model 230V 3 VA max model 12 24V 1 5 VA max Power supply 12 24 Va c 10 or 230Va 10 50 60 Hz Warning check the power supply specified on the instrument label for relay and power supply capacit...

Страница 5: ...ART function ALARMS folder with AL label Alarm type Parameter HA1 and LA1 modes as temperature absolute values or as differential compared to the Setpoint 0 absolute value 1 relative value Alarm Fan differential Alarm differential Power on Alarm Override Alarm exclusion time after instrument switch on after a power failure Setpoint Alarm Override Exclusion alarm time until Setpoint is reached 0 di...

Страница 6: ...from power on WARNING If set 0 it is not active if set 0 output will not be activated before this time Configuring digital inputs 0 disabled 1 SOFT START 2 Offset Setpoint 3 outputs stopped 4 not used 5 auxiliary output 6 stand by 7 maintenance requested 8 external alarm 9 external alarm stop regulators Polarity and Priority Digital Input no normally open nc normally closed noP normally open with ...

Страница 7: ...ulators if speci fied by the H11 9 parameter This alarm condition can be viewed in the AL folder with the label EA The relay can be silenced even if alarm icon starts blinking controls stay locked until the next time the digital input is deactivated DIAGNOSTICS DISPLAY E1 FAULT Faulty probe 1 thermostat control Table of faulty probes DISPLAY AH1 AL1 EA Opd Press any button to silence the alarm The...

Страница 8: ...ustomer Support Email techsuppeliwell invensys com Telephone 39 0437 986300 Climate Controls Europe An Invensys Company 11 2004 eng cod 9IS23094 SP1 SP1 dF1 dF1 Off On HC1 H SP1 dF1 SP1 dF1 Off On HC1 C HC1 Heat Cool Mode SP1 Setpoint 1 dF1 diFferential Relay 1 tripping differential ON OFF REGULATION DIAGRAM RS232 to PC RS485 BusAdapter PCInterface TTL PC with Televis package 230V N L 230V N L The...

Отзывы: