4.3.
Dimensions
Figure 4.1 E-PR-200 dimensions and Panel Mounting
4.4.
Panel Mounting
Punch a mounting cutout according to Figure 4.2 into the panel. Slide the device into the cutout from the
front of the panel. Fit the mounting clamps to the device, ensuring the lugs are located in their slots. Fasten
the mounting clamps using the retaining screws.
Figure 4.2 E-PR-200 Panel Cut Hole
ATTENTION
:
E-PR-200 device should be installed inside a suitable grounded metal
enclosure (panel). This must prevent the live parts being accessible to
human hands and metal tools.
(See Section 7. CONNECTION DIAGRAMS)
.
E-PR-200 does not include a power switch. Therefore, the power supply of
the device and power outputs must be wired through the proper fuse or
circuit breaker.
To minimize the pick-up of electrical noise, the wiring of low voltage
lines, particularly the sensor input should be routed away from the high-
current power cables. Where it is not possible, use shielded cables which
are grounded.
The cables used for powering the controller and the power outputs must
conform to the standards IEC 60245 and IEC 60227.