During operation
- 65 -
Error code
group
Meaning of the
group
Error
codes
Meaning of special errors Error
level
Meaning for technician
5xxh
Voltage errors
501h
502h
503h
504h
Voltage error on proces-
sor
4
Replace Safe Box
505h
Overvoltage on relay
supply
4
Replace Safe Box
506h
Undervoltage on relay
supply
1
Replace Safe Box
507h
Error in test of voltage
during relay test
4
Replace Safe Box
508h
Voltage error during
power up phase
4
Replace Safe Box
6xxh
Comparison
601h
Channel comparison of
door circuit input
3
This error can appear if the voltage on
door input was on the threshold be-
tween state “open” and state “closed”
for more than 3s.
This threshold are is round about 80 ...
105 V for the 110 V version and
140 V ... 200 V for the 230 V Version
Check voltage on door input. If it is too
low while the doors are closed, correct
this. If checking the voltage leads to no
results, supply the safety circuit with an
online sinewave UPS.
Remark/explanation:
It is likely that this fault is caused by
unusually high EMC disturbances on the
safety circuit. An online sine wave UPS
solves the problem because it consist-
ently delivers a pure sine wave, even if
the sinewave is severely disturbed.
602h to
625h
Internal channel compar-
ison of the other inputs
1
Replace Safe Box
630h to
632h
Shaft image corrupted
4
Replace Safe Box
640h
Comparison of floor
table and floor table as
received from the control
failed
1
Check the number and position of floors
stored in LIMAX Safe SG/SC and the
number and position of floors stored in
the lift control. The number of floors
must match. The floor positions stored
in LIMAX Safe SG/SC and in the control
must match with a tolerance of 50mm.
If this is not the case, correct the floor
table of the control or LIMAX Safe
SG/SC. If table of LIMAX Safe SG/SC
has to be corrected a new learn trip will
usually be necessary.
This error requires a special reset, see
chapter
8xxh
CANopen memory
area
There is a possibility that
CANopen has corrupted
the memory area for
safety relevant data.
4
Replace Safe Box
9xxh
1
OC test failed
901h
LIMAX Safe SG/SC stated
during
explicit
contact
test that OC is bridged in
a forbidden way.
2
2
Remove forbidden bridge OC_IN to
OC_OUT
1
only in case OC contact test is activated
2
although it is error level 2 NOC will open additionally to OC,
but opening of OC is not treated in the error level because the NOC will close again when lift is in recall