During operation
- 64 -
Error code
group
Meaning of the
group
Error
codes
Meaning of special errors Error
level
Meaning for technician
104h
Some position errors
appeared
1
Resetting the error without additional
measures is allowed but this is not
recommended because it is very likely
that the error will appear again.
The cause of the error can be the tape
or the sensor. As a first measure the
sensor should be replaced because this
is easier. If this does not help the tape
must be replaced.
105h
LIMAX33 RED/LIMAX44
RED gave signal that the
system has to be shut
down
4
Read out LIMAX33 RED/LIMAX44 RED –
log out. For evaluation see operation
manual LIMAX33 RED/LIMAX44 RED.
107h
Many errors in transmis-
sion between sensor and
Safe Box
4
First LIMAX33 RED/LIMAX44 RED
should be replaced. If this does not
help, replace the Safe Box.
106h
109h
10Ah
Heavy exception error
with unknown cause
4
Exchange complete system
2xxh
Internal plausibility
checks
4
Replace Safe Box
3xxh
Error in storing of
non-volatile values
in the EEPROM
Replace Safe Box
4xxh
Error when check-
ing relay feedback
404h
Feedback says that OC is
closed although there
was a request to open
4
Replace Safe Box
405h
Feedback says that NOC
is closed although there
was a request to open
4
Replace Safe Box
406h
Feedback says that SGC
is closed although there
was a request to open
4
Replace Safe Box
407h
Feedback says that OC is
has not closed although
there was a request to
close
1
In itself, this error is no imperative
reason for the Safe Box to be replaced.
The technician may reset the error and
see if it happens again. This error can
be caused be a strong mechanical
shock or vibration.
408h
Feedback says that NOC
is has not closed alt-
hough there was a
request to close
1
Same remarks as for error 407h are
valid here
409h
Feedback says that SGC
is has not closed alt-
hough there was a
request to close
1
Same remarks as for error 407h are
valid here
40Ah
Opening of SGC was
requested, but the exter-
nal feedback contact
says that the external
mechanical mimics is in
“release”-position
4
It is not allowed to go on operating the
lift without check.
Is has to be checked if the blocking
device really blocks the speed governor
when SGC is open and if the feedback
switch works correctly.
If no failure is found, it has to be as-
sumed that the Safe Box is defective and
has to be exchanged.
40Bh
Closing of SGC was
requested, , but the
external feedback contact
says that the external
mechanical mimics is in
“blocked”-position
1
Same remarks as for error 40Ah are
valid here