Technical Parameters
26
device
- Cable length for each input
max. 30 m
- LF pulse input
Terminals DI1, DI3
(DI3 – for gas meters with
the option of detecting the
rotation direction)
Terminals DI1, DI4
(DI4 – for gas meters
with the option of
detecting the rotation
direction)
- Maximum frequency
- Maximum operating flow rate Qm
10 Hz
36 000 m
3
/h
- Input type
Reed contact or potential-free output connection,
WIEGAND
- Min. pulse/delay time
40 ms
- No-load voltage
2.5 V ÷ 3.6 V
- Short-circuit current
approx. 3
A
- "ON"
R < 100 k
or U < 0.2 V
- "OFF"
R > 2 M
or U > 2.5 V
- Binary input, tamper contact
Terminals DI3
(Terminals DI1
13
)
Terminals DI4
- Input type
Low-power input, reed contact or potential-free
output connection
- Min. duration of the condition
100 ms
- No-load voltage
2.5 V ÷ 3.6 V
- Short-circuit current
approx. 3
A
- "ON" level
R < 100 k
or U < 0.2 V
- "OFF" level
R > 2 M
or U > 2.5 V
B. Non-Metrology
- Number
1
2
- Marking of the terminals (DIN
terminal block)
DI2
DI2, DI3
- Input options (SW configuration)
1 LF pulse input, or
1 binary input
2 LF pulse inputs, or
2 binary inputs, or
1 LF pulse input +
1 binary input
- Backup function in case of
power supply failure
No
- Cable length for each input
30 m max.
13
) Only when input DI1 is not used for gas meter connection (e.g. with the datalogger).
Содержание DATCOM
Страница 38: ...3 Technical Parameters 36 ...
Страница 45: ...5 Installation and Commissioning 43 5 1 2 ELCORplus corrector Fig 2 ELCORplus device dimensions ...
Страница 50: ...5 Installation and Commissioning 48 Fig 7 Examples of data plates ...
Страница 83: ...5 Installation and Commissioning 81 Fig 37 Communication via RS232 RS485 using B RS module ...
Страница 115: ...7 Technical Description of the Device 113 Fig 57 Functional diagram of ELCOR ...
Страница 116: ...7 Technical Description of the Device 114 Fig 58 Functional diagram of ELCORplus ...
Страница 122: ...7 Technical Description of the Device 120 Fig 61 Modem replacement ...
Страница 139: ...7 Technical Description of the Device 137 Fig 65 Volume and energy calculations calculation scheme ...
Страница 159: ...10 Communication with the Device 157 packet ...
Страница 174: ...12 Accessories 172 Fig 78 ELCORplus example of use of external modules ...
Страница 175: ...12 Accessories 173 Fig 79 ELCOR example of use of external modules Fig 80 ELCOR example of use of external modules ...
Страница 211: ...Appendix 2 ELCORplus version for Zone 2 209 Fig 86 Block diagram ELCORplus for zone 2 with ext 230V power supply ...
Страница 213: ...Appendix 3 Compass Data Export 211 Preview of generated document ...
Страница 215: ...Appendix 3 Compass Data Export 213 3 Export to XLS 4 Export to TXT DOC ...
Страница 216: ...Appendix 3 Compass Data Export 214 ...
Страница 217: ...Appendix 3 Compass Data Export 215 5 Export of graph ...