USER MANUAL RPS/M - 62000582 Rel.2.0
–
12/10/2018
2.2.
FUSES
Fuses can be used to protect power line of the RPS. It's recommended to use delayed fuses
according to the nominal input characteristic (see section 6.1).
2.3.
RCD PROTECTION
A residual-current device (RCD), or residual-current circuit breaker (RCCB), is a device that
instantly breaks an electric circuit to prevent serious harm from an ongoing electric shock.
It's recommended to
use B type
RCD with a earth leakage current of
30 mA
according to the
nominal input characteristic (see section 6.1).
2.4.
MAGNETO-THERMAL PROTECTION
The Magneto-thermal circuit breaker protect the input line from short circuits. Generally depends
on the load and on the connection (section and length of the cable).
It is recommended to use a magneto-thermal protection with
type C
curve according to the
nominal input characteristic (see section 6.1).