background image

15P0056B1

APPLICATION MANUAL     

AMS90/1

  

16/17

... cont.

  

INSTALLATION, CALIBRATION AND MAINTENANCE

INSTALLATION, CALIBRATION AND MAINTENANCE

CALIBRATION

The drive is usually delivered with preset calibrations, according to the data received
when ordering the unit, or based on the STANDARD CONFIGURATION.
If calibration data have to be checked or changed, proceed as follows:

a) Reduction of current limit below rating value:

1.  Disconnect one of the two cables powering term. 27-28 and insulate it.
2.  Connect an instrument for motor armature D.C. measurement.
3.  Send a speed reference with intermediate value, close the line remote control switch

and the RUN contact.

4.  Check the armature current value through the previously connected instrument, and,

if required, adjust the current value by rotating trimmer (RV7) 

I LIM

. The value

shown by the instrument must reach the required continuous value.

5.  If an ammeter is connected to terminal 12, check for data consistency, always

remembering that the unit sends a +10V

DC

 signal at rated current (10, 20 or 30A,

depending on the circumstances).

IMPORTANT:

 The last two operations should be performed in the shortest time. Finally, reset the

supply of the field rectifier circuit (term. 27-28).

  

b) Maximum speed calibration

1.  Start the machine by pressing the start push-button.
2.  Rotate the speed potentiometer to the max. value.
3.  Turn trimmer (RV9) 

n MAX

 so that the machine speed is at max. value, and check

that motor rating data, that is max. speed and max. armature voltage, is not
exceeded.

c) Speed ramp adjustment

1.  Rotate the potentiometer to the max. value.
2.  Start the drive.
3.  If the time required by the drive to reach the maximum speed (voltage) is too short

or too long, rotate trimmer (RV4) 

UP

. Otherwise, use trimmer  (RV5) 

DOWN

 to

adjust the slope. Note: the drive can control the slope only if the set ramp is longer
than the normal inertia slope (i.e. the one obtained through idle stop). Further, it can
control the rise, provided that it does not enter the current limit condition, i.e.
provided that the rise ramp is not too short.

... cont.

Содержание AMS90/1 Series

Страница 1: ...s no responsibility for the consequences resulting by the use of non original spare parts Elettronica Santerno reserves the right to make any technical changes to this manual and to the device without...

Страница 2: ...T NOTICE If after powering the unit closing the run contact and sending the speed reference the motor does not start check that the power circuit supply at term 23 24 has the SAME PHASE of the control...

Страница 3: ...h potentiometer Stability Internal or external current limit Armature compensation Acceleration and deceleration ramps Speed offset Light indicators Presence of supply direct voltages Current limit re...

Страница 4: ...rtical panel through 4 M4 screws Let a free space in the upper and lower side of the drive so as the cooling air can circulate To access the drive inside unscrew the two self tapping screws 3 5x9 5 us...

Страница 5: ...L2 Levelling impedance for form factor enhancement TC Auto transformer if any for D C motor field supply The alternate voltage VEA on the secondary is obtained from the direct voltage VEC through the...

Страница 6: ...15P0056B1 APPLICATIONMANUAL AMS90 1 6 17 Connect term 25 26 IN PHASE with term 23 24 respectively Fig 2 Power and supply connections diagram...

Страница 7: ...turn connect the earth to cable shield through a connection that should be as short as possible Always fit a NO auxiliary contact of KM remote control switch at terminal 18 as closure of KM remote con...

Страница 8: ...r module in case of undesired external short circuits Comply with the max prescribed value for I 2 t The L1 switching impedance is 35A 150 H ELETTRONICA SANTERNO code IM0100354 The current FF form fac...

Страница 9: ...rminals 21 22 in case of armature feedback RV7 I LIM Internal current limitation RV8 COMP Compensation for armature drop R x I Note in case of tacho generator feedback keep it in CCW position RV9 n MA...

Страница 10: ...reference of 0 10VDC J4 pos I Term 7 configured as ramp input for a current speed reference of 4 20mA current output from term 7 J5 pos I Inner adjustment of current limit J5 pos E External control o...

Страница 11: ...AMS90 1 APPLICATIONMANUAL 15P0056B1 11 17 Fig 4 ES719 control board layout n MIN SW1 UP n OUT I LIM n MAX STAB DOWN SW2 COMP n OFS J3 J4 J5 J2 TR3 15V LIM n 0 RUN...

Страница 12: ...RV6 up to 10VDC STANDARD calibration 10VDC at max speed 10VDC max 6mA max 12 I OUT Current signal output for possible ammeter STANDARD calibration 10VDC at drive rated current 10VDC max 6mA max 13 10V...

Страница 13: ...Hz with presetting by closing the two contacts of dip switch SW1 Note If required 415 440VAC supply voltages are available 10VA 27 28 Single phase supply STANDARD 400VAC max for inner rectifier for fi...

Страница 14: ...ctrostatic discharges level 3 EN 61000 4 2 Burst level 3 EN 61000 4 4 Surge level 3 EN 61000 4 5 Radio frequency electromagnetic fields 10V m IEC 1000 4 3 If malfunctions are detected in the devices i...

Страница 15: ...fter wiring check if connections and solderings are correct and check the proper positioning of jumpers and dip switches as regards the supply voltage and frequency and the drive application 4 Supply...

Страница 16: ...check for data consistency always remembering that the unit sends a 10VDC signal at rated current 10 20 or 30A depending on the circumstances IMPORTANT The last two operations should be performed in t...

Страница 17: ...current Note an excessive adjustment may cause instability f Speed offset calibration If with potentiometer at zero speed the motor rotates slowly unless a min reference has been applied to the potent...

Страница 18: ...of radio disturbance characteristics of industrial scientific and medical ISM radio frequency equipment EN61000 4 2 Electromagnetic compatibility EMC Part 4 Testing and measurement techniques Section...

Страница 19: ...nductor convertors General requirements and line commutated convertors Part 1 3 Transformers and reactors IEC146 6 Semiconductor convertors Part 6 Application guide for the protection of semiconductor...

Страница 20: ...CONVERTER OF AMS90 1 TYPE TO WHICH THIS DECLARATION RELATES APPLIED UNDER CONDITIONS SUPPLIED IN THE USER S MANUAL CONFORMS TO THE FOLLOWING STANDARDS OR NORMATIVE DOCUMENTS EN60204 1 Safety of machi...

Отзывы: