APPLICATION MANUAL     

AMS90/1

  

10/17

... cont.

 

ES719 CONTROL BOARD DESCRIPTION

ES719 CONTROL BOARD DESCRIPTION

             (see fig. 4)

PRESET JUMPERS

PRESET JUMPERS

(Pos. STANDARD:  J2 

 

400

,  J3 

 

L

,  J4 

 

V

,  J5 

 

I

)

J2 

pos. 230

  

230Vac supply at terminals 25 and 26.

J2 

pos. 400

400Vac supply at terminals 25 and 26.

   

NOTE:

 If required, our transformer with code TR0102121 (instead of TR0102122) can be installed

as transformer TR3 to supply with voltage the terminals 25 and 26, according to the position of jumper J2,
415Vac or 440Vac.

J3 

pos. L

  

   Drive enabling at term. 18 (RUN) closing towards 0V, through insulated

relay contact or NPN transistor.

J3 

pos. H

 

Drive enabling at term. 18 (RUN) closing towards a positive voltage of
0…30V

DC

, through insulated relay contact or NPN transistor.

J4

 

pos. V

Term. 7 configured as ramp input for a voltage speed reference of
0…+10V

DC

.

J4

 

pos. I

Term. 7 configured as ramp input for a current speed reference of
4…20mA (current 

output 

from term. 7).

J5 

pos. I

  

     Inner adjustment of current limit.

J5 

pos. E

External control of current limit.

SELECTION DIP-SWITCHES

SELECTION DIP-SWITCHES

(Pos. STANDARD:  SW1(1+2) 

 

OFF

,  SW2(1+2+3+4) 

 

OFF

)

SW1 contacts 1+2 

 OFF

         

(bottom contacts)

Presetting for mains supply with 50Hz frequency.

SW1 contacts 1+2 

 ON

        

 

(top contacts: 

60

)

Presetting for mains supply with 60Hz frequency.

SW2 contacts

 

1+2+3+4 

 OFF

          (bottom contacts)

Presetting for tacho generator feedback at
terminals 1 and 2.

SW2 contacts 1+2+3+4 

 ON

          (top contacts: 

ARM

)

Presetting of armature feedback, at high
impedance. In this case, the tacho generator signal
should NOT be present at term. 1 and 2.

Note: act on contacts SW2 only when term. 25-26 are NOT
supplied.

Note: under TACHO GENERATOR feedback, if you close 

only

the key no. 4 (the right one) of SW2, you LOWER the max.
speed range, which can be obtained through trimmer RV9 (n
MAX) – up to 16…92V

DC

 at term. 1-2.

Содержание AMS90/1 Series

Страница 1: ...s no responsibility for the consequences resulting by the use of non original spare parts Elettronica Santerno reserves the right to make any technical changes to this manual and to the device without...

Страница 2: ...T NOTICE If after powering the unit closing the run contact and sending the speed reference the motor does not start check that the power circuit supply at term 23 24 has the SAME PHASE of the control...

Страница 3: ...h potentiometer Stability Internal or external current limit Armature compensation Acceleration and deceleration ramps Speed offset Light indicators Presence of supply direct voltages Current limit re...

Страница 4: ...rtical panel through 4 M4 screws Let a free space in the upper and lower side of the drive so as the cooling air can circulate To access the drive inside unscrew the two self tapping screws 3 5x9 5 us...

Страница 5: ...L2 Levelling impedance for form factor enhancement TC Auto transformer if any for D C motor field supply The alternate voltage VEA on the secondary is obtained from the direct voltage VEC through the...

Страница 6: ...15P0056B1 APPLICATIONMANUAL AMS90 1 6 17 Connect term 25 26 IN PHASE with term 23 24 respectively Fig 2 Power and supply connections diagram...

Страница 7: ...turn connect the earth to cable shield through a connection that should be as short as possible Always fit a NO auxiliary contact of KM remote control switch at terminal 18 as closure of KM remote con...

Страница 8: ...r module in case of undesired external short circuits Comply with the max prescribed value for I 2 t The L1 switching impedance is 35A 150 H ELETTRONICA SANTERNO code IM0100354 The current FF form fac...

Страница 9: ...rminals 21 22 in case of armature feedback RV7 I LIM Internal current limitation RV8 COMP Compensation for armature drop R x I Note in case of tacho generator feedback keep it in CCW position RV9 n MA...

Страница 10: ...reference of 0 10VDC J4 pos I Term 7 configured as ramp input for a current speed reference of 4 20mA current output from term 7 J5 pos I Inner adjustment of current limit J5 pos E External control o...

Страница 11: ...AMS90 1 APPLICATIONMANUAL 15P0056B1 11 17 Fig 4 ES719 control board layout n MIN SW1 UP n OUT I LIM n MAX STAB DOWN SW2 COMP n OFS J3 J4 J5 J2 TR3 15V LIM n 0 RUN...

Страница 12: ...RV6 up to 10VDC STANDARD calibration 10VDC at max speed 10VDC max 6mA max 12 I OUT Current signal output for possible ammeter STANDARD calibration 10VDC at drive rated current 10VDC max 6mA max 13 10V...

Страница 13: ...Hz with presetting by closing the two contacts of dip switch SW1 Note If required 415 440VAC supply voltages are available 10VA 27 28 Single phase supply STANDARD 400VAC max for inner rectifier for fi...

Страница 14: ...ctrostatic discharges level 3 EN 61000 4 2 Burst level 3 EN 61000 4 4 Surge level 3 EN 61000 4 5 Radio frequency electromagnetic fields 10V m IEC 1000 4 3 If malfunctions are detected in the devices i...

Страница 15: ...fter wiring check if connections and solderings are correct and check the proper positioning of jumpers and dip switches as regards the supply voltage and frequency and the drive application 4 Supply...

Страница 16: ...check for data consistency always remembering that the unit sends a 10VDC signal at rated current 10 20 or 30A depending on the circumstances IMPORTANT The last two operations should be performed in t...

Страница 17: ...current Note an excessive adjustment may cause instability f Speed offset calibration If with potentiometer at zero speed the motor rotates slowly unless a min reference has been applied to the potent...

Страница 18: ...of radio disturbance characteristics of industrial scientific and medical ISM radio frequency equipment EN61000 4 2 Electromagnetic compatibility EMC Part 4 Testing and measurement techniques Section...

Страница 19: ...nductor convertors General requirements and line commutated convertors Part 1 3 Transformers and reactors IEC146 6 Semiconductor convertors Part 6 Application guide for the protection of semiconductor...

Страница 20: ...CONVERTER OF AMS90 1 TYPE TO WHICH THIS DECLARATION RELATES APPLIED UNDER CONDITIONS SUPPLIED IN THE USER S MANUAL CONFORMS TO THE FOLLOWING STANDARDS OR NORMATIVE DOCUMENTS EN60204 1 Safety of machi...

Отзывы: