8.5 Additional features
8.5.1 Reset
To reset the device to its factory setup:
- select the voice RESEt from the main menu (see cap. 8.3);
- select YES pressing the key
ORG
(pressing the key the visualized value toggle
between YES and no);
- press the key
SET
to confirm.
8.5.2 Calibration
The Calibration voice in the main menu activates the
CALIBRATION MODE
and the display shows
GO
.
At this point, the user must slowly move the sensor in one direction along the
magnetic band.
After the
GO
it will be displayed a progress bar that will grow as long the sensor
is moved. The procedure end when the position measurement is shown again
by the display.
This operation allow the sensor to be accurately bound to the magnetic tape and
have to be done every time after the installation of the sensor.
8.5.3 Test LCD
The
LcdtESt
voice in the main menu allow to switch on all the display segments.
P r O G _ t G
PtrG 01
…
PtrG 32
L o a d _ t G
LtrG 01
LtrG 32
…
8.4 Target menù tree
Scrolling menu
direction
If mm
-9999.99÷9999.99
If inch
-9999.99÷9999.99
If Deg
-99999÷99999
ORG
ABS-REL