Operating and assembly instructions HRD

www.elektror.com

9016309 01.20/13

which are operated in these environments must be inspected 

on a regular basis.

Protection by residual-current-operated circuit breaker 

(FI circuit-breaker):

The present IGBT frequency converters produce discharge 

currents of >=3.5 mA due to their design principle. These dis-

charge currents can lead to unwanted tripping in systems 

protected by a 30 mA-FI circuit-breaker. 
If a fault occurs, fault currents can also discharge through the 

PE conductor as direct current. If protection is needed on the 

supply side by means of an FI circuit-breaker, then an ACDC 

sensitive (type B) FI circuit-breaker must be used. Use of an 

FI circuit-breaker other than type B can cause death or seri-

ous injury if a fault occurs. 
To meet the EN 61800-5-1 standard, the PE conductor must 

be duplexed and routed through separate terminals or have 

a cross-section of at least 10 mm² Cu.

Operation and connection to public grids:

See 3.6

4.3 Hydraulic Motor Operation

The run-up and expiry times as well as the speed changes 

speci

fi

 ed in 4.2 should be noted when operating with hydrau-

lic motors. Free-running hydraulic motors should be used to 

guarantee a smooth run on.

5 INSTRUCTIONS FOR MAINTENANCE

Wearing parts are subject to the recommended maintenance 

intervals (refer to 5.1 to 5.5). The service life of wearing parts 

(ball bearings and 

fi

 lters) depends on the operating hours, 

the load and other in

fl

 uences, such as temperature, etc.

Maintenance and servicing may only be performed by per-

sons with the necessary expertise and regular training. In ad-

dition to the appliance’s operating instructions and the regu-

lations and recommendations for the system as a whole, the 

following points should be observed:

Inspection and maintenance intervals:  

The operator must set the cleaning, inspection and mainte-

nance intervals himself according to operating hours, load 

and operating conditions.

Immediate inspection and maintenance:

The blower must be inspected immediately if vibrations or 

reduced air 

fl

 ow are observed.

Note!

Repairs must be carried out by the manufacturer. 

We cannot accept any liability for repairs carried 

out by third parties.

5.1 Ball bearings

Note!

The fans from Elektror are equipped with sealed 

deep groove ball bearings, which do not require 

relubrication.

Note!

Check the ball bearings during servicing and 

prior to recommissioning.

Operation is only permitted with 

fl

 awless ball 

bearings!

Note!

In the event of frequently starting up and shutting 

down, premature replacement of the bearings will 

be required. Determining the time for replacing 

the bearings is the sole responsibility of the main-

tenance and servicing personnel, who must make 

a safety judgement.

Devices

Minimum ball bearing service 

life

Horizontal 

motor shaft

Vertical motor 

shaft

HRD range

22.000

hours

11.000

hours

Ball bearing change recommendation

 

- Prior to reaching the minimum service life

 

- 30 months following delivery at the latest

 

- Check after 6 months’ storage time; change if necessary

5.2 Seals and radial shaft sealing rings

Sealing elements and shaft sealing rings must, for safety rea-

sons, always be replaced after maintenance work involving 

opening, removing or otherwise modifying sealing elements.

5.3 Micro-

fi

 lters

The degree of clogging of the 

fi

 lter mats must be checked at 

regular intervals in dependence on the conditions of use or 

ambient conditions and any applicable environmental protec-

tion guidelines. This means that the user is responsible for 

ensuring that the 

fi

 lters are permeable.

5.4 V-belt (in appliances supplied complete with V-belt 

     drive)

The minimum service life of the V-belt in use is 25,000 hours. 

The V-belt tension must be checked after approximately 

5,000 operating hours (refer to label for belt tension values 

and setting values). New V-belts must be checked after a 

running-in period of 2 hours and retensioned if necessary 

(data see chapter 11 technical speci

fi

 cations).

dg

dk

Sa

f

Trum

ca. e

ca. e/2

E a

Checking and retensioning the V-belt

The item numbers given in brackets refer to the replacement 

part drawing. Setting values: see label on the support 

fl

 ange 

plate (59) respectively on the blower base (11).

Replacing/retensioning the V-belt:

•  Remove the grating (55) or belt guard (27).
•  Undo the hexagon bolt (60) or tensioning bolt on the 

  motor tensioning rail (43).
• Undo the hexagon bolt (58) or tensioning bolt on the 

  motor tensioning rail (43).

Содержание HRD 1/2T

Страница 1: ...ilatoren Betriebs und Montageanleitung DE Elektror High Pressure Blowers Operating and assembly instructions EN HRD 1 2T HRD 1 3T HRD 1 4T HRD 1 5T HRD 14 5T HRD 2 3T HRD 2 4T HRD 2 5T HRD 60 4 HRD 60...

Страница 2: ...n Ventilator ausgefiltert werden Bei Kondensatbildung empfehlen wir eine Kondenswasser bohrung an der tiefsten Stelle im Geh use Der Einsatz f r aggressive abrasive klebende giftige explosionsf hige o...

Страница 3: ...sofern vorhanden gilt f r Ventilatoren mit Motor und Riementrieb Warnung Der Riementrieb ist mit einem Schutzgitter abge deckt Den Ventilator niemals in Betrieb nehmen wenn das Schutzgitter nicht ange...

Страница 4: ...r Riemenschutz angebracht und fest verschraubt ist Verletzungsgefahr 1 14 Elektrische Gef hrdungen Gefahr Gefahr durch elektrischen Strom Spannungsf hrende Bauteile stehen unter Strom und verursachen...

Страница 5: ...hriften selbst zu sorgen Die Aufstellung von Serien Ventilatoren mit senkrechter Antriebswelle ist bei HRD Ventilatoren bis zu folgenden Typen m glich Mit Tr gerflanschgeh use Maximal bis HRD 2 5 T FU...

Страница 6: ...wischen Motor und Schaltschrank Frequenzumrichter z B Lenze Vector Omron MX2 und Omron RX darf 20 m nicht bersteigen Bei motornah montierten Frequenzumrichtern vom Typ Kostal INVEOR sind maximale Leit...

Страница 7: ...gnetische Vertr glichkeit 2014 30 EU unter Ber cksichtigung der Norm EN 61800 3 Kategorie C2 Industriebereich Warnung In einer Wohnumgebung kann dieses Produkt hochfrequente St rungen verursachen die...

Страница 8: ...dingt Ableitstr me 3 5 mA Diese Ableitstr me k nnen zu Fehlausl sungen in Anlagen f hren die ber einen 30 mA FI Schutzschalter abgesichert sind Im Fehlerfall k nnen Fehlerstr me auch als Gleichstrom b...

Страница 9: ...iben achten Riemenspannung nach Hinweisschild mit Sechskant schraube 58 einstellen Sechskantschraube 60 bzw Fixierschraube an Motor Spannschiene 43 anziehen Abdeckgitter 55 bzw Riemenschutz 27 anbring...

Страница 10: ...ihrer Ger te und Komponenten ab Dies gilt insbesondere auch f r besondere Verwendungen und Einsatzbedingungen die nicht ausdr cklich mit der Fa Elektror abgestimmt wurden Elektror lehnt zudem jede Haf...

Страница 11: ...schinenrichtlinie Die Inbetriebnahme der unvollst ndigen Maschine ist so lange untersagt bis festgestellt wurde dass die Maschine in die die unvoll st ndige Maschine eingebaut werden soll den Bestimmu...

Страница 12: ...he housing in the event of the formation of condensation Use of the blowers for aggressive abrasive sticky toxic potentially explosive or very moist media is not permissible The maximum temperature of...

Страница 13: ...uit breaker this does not apply to frequency converter operated appliances Where appliances are frequency converter operated the existing temperature sensor PTC resistor sensor or temperature switch n...

Страница 14: ...y Only use hoists and load suspension devices with su cient load carrying capacity Secure the route of transportation Note The eye bolt on the motor must not be used to lift the entire blower This is...

Страница 15: ...models suitable for frequency converters FUK models devices with UL approv al devices with Aircontrol and other motor makes Ambient temperature 20 C to 40 C Voltage tolerance 5 For exceptions see 4 2...

Страница 16: ...g the direction of rotation Switch on the blower The running direction of the impeller should correspond to the direction arrow on the housing If the impeller rotates in the wrong direction then inter...

Страница 17: ...or operation The values for the maximum minimum frequency can be found at 1 11 The converter should have a connection for a tempera ture sensor PTC resistor sensor or a temperature switch normally clo...

Страница 18: ...he manufacturer We cannot accept any liability for repairs carried out by third parties 5 1 Ball bearings Note The fans from Elektror are equipped with sealed deep groove ball bearings which do not re...

Страница 19: ...sure that all tools or other foreign objects have been removed from inside the device and that all covers and protective grilles have been attached correctly 6 SAFETY RELATED INFORMATION ON TAKING OU...

Страница 20: ...tive The commissioning of the partially completed machine is not permitted until it has been verified that the machine in which the partially completed machine is to be installed complies with the pro...

Страница 21: ...21 www elektror de Betriebs und Montageanleitung HRD 9016309 01 20 13 DE...

Страница 22: ...riebs und Montageanleitung HRD www elektror de 9016309 01 20 13 DE 9 EXPLOSIONSZEICHNUNG BROKEN VIEW DRAWING Geh usestellungen Die Geh usestellung des Ventilators ist f r die Bestellung einiger Ersatz...

Страница 23: ...EN Pos Benennung Designation 1 Schraube Screw 2 Schutzgitter Wire mesh guard 3 Schraube Screw 4 Geh usedeckel Housing cover 5 Schraube Screw 6 Scheibe Disc 7 Laufrad Impeller 8 Ventilatorgeh use Blow...

Страница 24: ...80 7 80 6 76 9 22 5 85 89 6205 6202 6204 IE3 8 0 4200 3430 2 5500 230 400 60 3 55 2 05 0 90 77 0 81 9 80 6 21 85 89 6205 6202 6204 NEMA 4 8 0 4200 3430 2 5500 277 480 60 2 95 1 71 0 90 77 0 81 9 80 6...

Страница 25: ...4 72 91 96 6206 6306 NEMA 4 52 0 5900 3525 4850 480 60 7 60 4 80 89 5 89 6 88 4 72 91 96 6206 6306 HRD 65 5 IE3 56 0 7500 2940 5300 400 50 10 2 5 50 89 2 90 6 90 0 80 94 99 6206 6306 IE3 56 0 7700 354...

Страница 26: ...Conti Axial spacing theor value Hz number N mm mm mm mm HRD 1 2T 71 L 2 6205 6202 6202 50 XPZ 1 25 3 562 124 71 L 2 6205 6202 6202 60 XPZ 1 25 3 562 141 HRD 1 3T 71 L 2 6205 6202 6202 50 XPZ 1 25 3 63...

Страница 27: ...4 800 196 HRD 65 5 132 SX 2 6206 6308 50 XPZ 2 25 5 800 195 132 SX 2 6206 6206 6308 60 XPZ 2 25 5 812 189 HRD 65 7 132 SL 2 6206 6308 50 XPZ 2 25 3 800 179 132 SL 2 6206 6206 6308 60 XPZ 2 25 3 812 1...

Страница 28: ...5 4 15 2 40 1 1 17 21 85 94 6204 HRD 14T FU K 105 1 5 16 5 4900 6075 230 400 105 5 70 3 30 1 5 19 23 85 94 6204 HRD 14T FU K 105 2 2 24 0 4900 6140 230 400 105 6 90 4 00 2 2 22 26 85 94 6205 HRD 16T F...

Страница 29: ...hnung 2 Gesamt vorspann kraft Dynamische Wellen belastung Ventilator Laufrad seitig Ventilator Riemen seitig Type Volumetric fl ow rate Total pressure di erence Max permit ted blower speed Power deman...

Страница 30: ...itig Kugellagerbezeichnung wenn Elektror Motor Gesamtvorspannkraft Dynamische Wellenbelastung Type Motor type Ball bearing designation impeller side Ball bearing designation belt side Ball bearing des...

Страница 31: ...148 152 121 125 HRD 1 4 T 148 152 121 125 HRD 1 5 T 160 164 134 138 HRD 14 2 T 121 125 102 106 HRD 14 3 T 134 138 112 116 HRD 14 4 T 148 152 121 125 HRD 14 5 T 160 164 130 134 HRD 2 3 T 121 125 102 1...

Страница 32: ...Name o cial registration no Place of business Product model no Nominal motor input power V when under pressure at optimal energy e ciency kW Volumetric fl ow rate at optimal energy e ciency m3 min Tot...

Страница 33: ...4 2 3 4 HRD 2T FU 95 3 0 95 3 07 15 1 7435 5600 1 07 5 5 6 61 0 B 1 66 4 2 3 4 HRD 2T FUK 95 3 0 95 3 07 15 1 7435 5600 1 07 5 5 6 65 4 B 1 68 2 2 3 4 HRD 60 FU 105 4 0 105 5 41 20 9 10160 6190 1 10 5...

Страница 34: ...1 4T 60 0 87 5 8 3930 3500 5500 1 04 5 5 6 46 7 B 1 51 1 2 3 4 HRD 1 5T 50 1 03 6 1 4670 2880 6020 1 04 5 5 6 46 8 B 1 50 8 2 3 4 HRD 1 5T 60 1 12 6 6 4560 3500 6090 1 04 5 5 6 60 6 B 1 68 8 2 3 4 HRD...

Страница 35: ...6 63 5 B 1 65 7 2 3 4 HRD 65 5 60 6 18 32 0 7360 3540 5430 1 07 5 5 6 65 4 B 1 66 6 2 3 4 HRD 65 7 50 6 36 36 3 8090 2930 5830 1 08 5 5 6 65 0 B 1 65 6 2 3 4 HRD 65 7 60 7 16 43 7 7590 3510 5800 1 07...

Страница 36: ...Beschreibung FU Mit diesem Ventilator muss eine Drehzahlregelung installiert werden FUK In diesem Ventilator ist eine Drehzahlregelung integriert 1 total e ciency grade 2 3 refer to rating plate 4 El...

Страница 37: ...37 www elektror de Betriebs und Montageanleitung HRD 9016309 01 20 13 DE...

Страница 38: ...38 Betriebs und Montageanleitung HRD www elektror de 9016309 01 20 13 DE...

Страница 39: ...39 www elektror de Betriebs und Montageanleitung HRD 9016309 01 20 13 DE...

Страница 40: ...Internet unter www elektror de Gerne steht Ihnen auch unser Produktmanagement unter der Rufnummer 49 711 31973 1111 zur Verf gung You will find further information about our products on the internet...

Отзывы: