ELECTRONET
UM-ELMAG 200-R3
PAGE 31 OF 34
Sr.
No.
Function
Code
Command
Register
Address
Details
Data Format
1
0x04
Read holding
Register
40011
40012
40010
40013
40011
40012
Value = Reverse Flow Totaliser
MSbyte
LSbyte
Downloading Status
0x0000 = No Downloading
0xFFFF = Downloading in process
Integer (Hex)
Reverse Flow Enable / Disable
0 = Disable
1 = Enable
Integer (Hex)
40014
Current Flow Direction
0 = Forward
1 = Reverse
Integer (Hex)
11.2 To Set Data downloading Flag :
1. Baud Rate : 9600 / 19200 / 38400 / 4800
2. Parity : None/Odd/Even
3. Start Address : 10
4. Slave Address : Selectable 01 to 99
5. Function : 04
6. Display Data : Hex
7. Length : 01
8. Communication Protocol: Modbus RTU
Double click at address 10 and select function 0x06 & write download flag =1
Swapped Float