ELECTRONET
UM-ELMAG 200-R3
PAGE 30 OF 34
11. MODBUS (RS 485) COMMUNICATION DETAILS
Sr.
No.
Function
Code
Command
Register
Address
Details
Data Format
1
0x04
Read holding
Register
40001
40003
40002
40004
40005
40006
40007
40008
Swapped Float
40001
40003
40002
40004
Value = Flow Rate
MSbyte
MSbyte
LSbyte
LSbyte
40009
Flow
totaliser
Flow Decimal Value
0 = 0000
1 = 000.0
2 = 00.00
3 = 0.000
Integer (Hex)
Flow Volume Unit Value
0 = Ft3
1 = gal
2 = Ltr
3 = m3
4 = ML
Integer (Hex)
Flow Time Unit Value
0 = Sec
1 = Min
2 = Hr
3 = Day
Integer (Hex)
Totaliser Decimal Value
0 = 0000
1 = 000.0
2 = 00.00
3 = 0.000
Integer (Hex)
Totaliser Engg. Unit Value
0 = Ft3
1 = gal
2 = Ltr
3 = m3
4 = ML
Integer (Hex)
Note
: Program below parameters before starting communication
1. Baud Rate :9600 / 19200 / 38400 / 4800
2. Parity : None/Odd/Even
3. Slave Address : Selectable 01 to 99
4. Length : 14
5. Communication Protocol: Modbus RTU
11. 1 To view parameters :
COMMUNICATION FORMAT
Swapped Float