4. The flow sensor should always be filled with liquid. For that reason the flow sensor must not be
mounted at the highest point of the pipe system or in free outlets, where gravity could empty or
partially empty the pipe.
5. The flow sensor can be mounted vertically or horizontally . If the flow sensor is mounted
vertically , the flow direction should always be upwards. In that way the effect from possible
bubbles in the liquid will be significantly reduced, just as it will ensure that the flow sensor is
always filled with liquid. In case the liquid is carrying particles, for example when measuring
sludge, sewage, etc.,the flowsensor must be mounted vertically .