ohmmeter can be used. 

Always discharge the cell with 

a screw driver before testing with an ohmmeter. 

1.  With  the  ohmmeter  set  on  its  lowest  scale,  take  a 

reading  between  the  top  center  contact  of  the  cell 
and the ionizing fingers on the bottom of the cell. You 
should have continuity. If you do not, then there is a 
bad  contact  between  the  center  contact  and  the  top 
set of ionizing fingers. 

2.  Test  the  resistance  between  the  top  center  contact 

and  the  cell  frame.  You  should  read  infinite 
resistance.  If  not,  you  have  a  short  in  the  ionizing 
section. 

3.  Take a reading between the two outside contacts on 

the top of the cell. You should have continuity. If you 
do  not,  then  there  is  a  bad  contact  between  one  of 
the  contacts  to  the  live  cell  plate.  Test  each  top 
outside  contact  to  the  last  plate  in  the  cell  to 
determine which contact is not mating properly. 

4.  Test the resistance between the outside contacts and 

the cell frame. You should read infinite resistance. If 
not, you have a short in the collecting section. 

 

Removing Power Box 

1.  Turn the main system switch 

OFF

 or disconnect the 

power cord. 

2.  Remove the power box cover. 
3.  If  the  unit  does  not  have  a  cord  disconnect  the 

source wires to the Air Cleaner. Cap off the wires so 
the system can still be operated. 

4.  Remove  the  two  nuts  holding  the  power  box  to  the 

cabinet.  

5.  Slide  the  power  box  forward  then  up  to  remove  it 

from the cabinet. 

6.  If  you  are  removing  the  power  box  for  any  length  of 

time tape a cover over the top opening to prevent air 
from entering into the system. 

 
Replacing A Tungsten Ionizing Wire 

Replacement wires are cut to the correct length and 

have eyelets at each end for easy replacement. 
1.  Turn 

OFF

 power to Air Cleaner. 

2.  Remove cell from Air Cleaner. 
3.  Remove  all  parts  of  broken  wire  from  the  cell.  If 

necessary, the cell may be used temporarily with one 
wire missing until a replacement is received. 

4.  Place  one  end  of  the  loop  over  the  finger  at  the 

bottom of the cell.  

5.  Using needle-nose pliers, grip the other end of  wire, 

near  the  bottom  of  the  top  loop.  Pull  the  wire  up 
toward  the  top  finger.  As  you  apply  tension,  the 
bottom finger will give, allowing the placement of the 
loop around the top finger. 

6.  Install cell in Air Cleaner. 

10 

Fig. 7 

 Exploded View 

Use Part Numbers When Ordering (See Separate Parts List) 

Part Description 

On/Off Switch 

Safety Interlock Switch 

Performance Indicator Light (Green LED) 

Air Proving Switch 

24 Volt Transformer 

Power Board 

Fibreboard (with 4 Copper Contacts) 

Copper Contact 

Cord Assembly (Optional) 

10  Lid for Power Box 

11  Power Box Complete 

12  Carbon Filters (Set of 3) 

13  Prefilter 

14  Cell Guide (Plastic) 

15  Collecting Cell 

16  Cell Handle 

17  Door (with Plastic Clip & Handle) 

18  Door Handle (Plastic) 

19  Ionizing Wire 

20  Male & Female Door Clip Set 

Содержание EASASD-10ASC

Страница 1: ...rease mold fungi bacteria viruses and more down to 0 01 micron Dual Voltage Aluminum Collecting Cells are durable and easy to maintain Cell Guide ensures proper placement of collecting cells Activated...

Страница 2: ...of electrostatic precipitation Millions of airborne pollutants are carried through the return air ducts of the heating cooling system and treated through four stages of filtration The prefilters 2 re...

Страница 3: ...the Air Cleaner will vary with CFM and whether the carbon filters have been installed in the unit Location The Air Cleaner must only be installed in the return air duct as close to the fan compartment...

Страница 4: ...ifier must be installed as far from the Air Cleaner as possible 2 Collecting cells must be washed frequently to prevent a mineral deposit build up Installation Location With Air Conditioner Whenever p...

Страница 5: ...ent direction than the left to right set up The handle should face the door Close access door Wiring Wiring should only be performed by qualified personnel only All wiring must comply with all applica...

Страница 6: ...a non chlorine non corrosive non abrasive liquid household detergent Allow detergent to run down both sides of plates and ionizing wires Let stand for 5 minutes or fill up laundry tub with water and...

Страница 7: ...igh Voltage At Power Board A high voltage meter capable of measuring up to 10 000 VDC is required to test the voltage 1 The Air Cleaner should be ON with the cells installed the door closed and the sy...

Страница 8: ...e performance light will come on The light on the power switch will be lit even when the APS is open If the power board fails to come on with the fan on check that the sensor is properly set down to t...

Страница 9: ...ner 8 Remove the high voltage meter 9 Replace the power box cover 10 Turn ON the Air Cleaner Setting Approximate Voltage Without High Voltage Meter A high voltage meter should be used to set the high...

Страница 10: ...olding the power box to the cabinet 5 Slide the power box forward then up to remove it from the cabinet 6 If you are removing the power box for any length of time tape a cover over the top opening to...

Страница 11: ...options with power box 12 Carbon Filters Set of 3 1156 3 1156 3 1856 3 1856 3 13 Prefilter R0 0855 R1 0855 R2 0855 R8 0855 14 Cell Guide Plastic R1 0603 R1 0603 R1 0603 R1 0603 15 Collecting Cell D0 0...

Страница 12: ...making good connection on cell With needle nose pliers gently pull contacts down or replace contacts Cells arcing excessively power light and per formance indicator light ON or flashing Cells wet fro...

Страница 13: ...basis for the Air Cleaner to function at its peak of efficiency The frequency of cleaning will vary from one house to another On average the cells should be cleaned every 3 months Use the chart below...

Страница 14: ...NOTES 14...

Страница 15: ...pairing removing installing shipping servicing or handling of either defective parts or replacement parts Such costs may be covered by a separate warranty provided by the dealer LIMITATIONS OF WARRANT...

Страница 16: ...of the furnace or air handler ensure that there is 115 Volt output from these terminals when the unit is run manually and is running on low speed Some manufacturers do not supply full output voltage...

Отзывы: