Adding refrigerant
Refrigerant must be added if the piping measures more
than 5 metres (16'5") in length. This operation can only
be performed by a professional F-Gas engineer, for the
additional gas amount, see the below
Gas leakage inspection
After the pipeline connection is done, use a leakage inspection device to carefully check if
there is any leakage at the joints. This is an important step to ensure the quality of
installation. Once a leak is detected, proper action should be taken immediately.
1. For good drainage, the drain hose should be angled downwards.
2. Do not pull on or bend the drain hose or flood its end with water.
3. When the long drainage hose passes through indoor areas, it should be wrapped in insulation.
17
Additional refrigerant amount
Liquid pipe diameter 6.35 (1/4")
Liquid pipe diameter: 9.52 (3/8")
(piping length-5)mx30g
or (piping length-16)ftx0.3oz
(piping length-5)mx65g
Or (piping length-16)ftx0.7oz