15
15
EN
ELAN3
SNMP Ethernet Controller
5.2.3.
SNMP
Parameter name
OID
Access
Value
Example / comment
SysDescription
1.3.6.1.2.1.1.1.0
get/set
text (32 chars max.)
e.g. Inputs monitoring SNMP device
SysObjectID
1.3.6.1.2.1.1.2.0
get
1.3.6.1.4.1.34093.1.2
constant
SysUpTime
1.3.6.1.2.1.1.3.0
get
counter
e.g. 10778 seconds
SysContact
1.3.6.1.2.1.1.4.0
get/set
text (32 chars max.)
e.g. ELDES, Tel. No. +370111111
SysName
1.3.6.1.2.1.1.5.0
get/set
text (32 chars max.)
e.g. ELAN3-SNMP device
SysLocation
1.3.6.1.2.1.1.6.0
get/set
text (32 chars max.)
e.g. Vilnius, Lithuania
Read/write community
1.3.6.1.4.1.34093.1.2.30.1.0
get/set
text (16 chars max.)
e.g. public
Trap Destination1
1.3.6.1.4.1.34093.1.2.31.1.0
get/set
IP address
e.g. 192.168.1.201
Trap Destination2
1.3.6.1.4.1.34093.1.2.31.2.0
get/set
IP address
e.g. 192.168.1.202
Trap Destination3
1.3.6.1.4.1.34093.1.2.31.3.0
get/set
IP address
e.g. 192.168.1.203
5.2.4.
Inputs
Parameter name
OID
Access
Value
Example / comment
Input1 name
1.3.6.1.4.1.34093.1.2.60.1.0
get/set
text
e.g. Input-1
Input2 name
1.3.6.1.4.1.34093.1.2.60.2.0
get/set
text
e.g. Input-2
Input3 name
1.3.6.1.4.1.34093.1.2.60.3.0
get/set
text
e.g. Input-3
Input4 name
1.3.6.1.4.1.34093.1.2.60.4.0
get/set
text
e.g. Input-4
Input1 state ON name
1.3.6.1.4.1.34093.1.2.61.1.0
get/set
text
e.g. Input-1 is violated
Input2 state ON name
1.3.6.1.4.1.34093.1.2.61.2.0
get/set
text
e.g. Input-2 is violated
Input3 state ON name
1.3.6.1.4.1.34093.1.2.61.3.0
get/set
text
e.g. Input-3 is violated
Input4 state ON name
1.3.6.1.4.1.34093.1.2.61.4.0
get/set
text
e.g. Input-4 is violated
Input1 state OFF name
1.3.6.1.4.1.34093.1.2.62.1.0
get/set
text
e.g. Input-1 is restored
Input2 state OFF name
1.3.6.1.4.1.34093.1.2.62.2.0
get/set
text
e.g. Input-2 is restored
Input3 state OFF name
1.3.6.1.4.1.34093.1.2.62.3.0
get/set
text
e.g. Input-3 is restored
Input4 state OFF name
1.3.6.1.4.1.34093.1.2.62.4.0
get/set
text
e.g. Input-4 is restored
Input1 priority
1.3.6.1.4.1.34093.1.2.63.1.0
get/set
1... 8
e.g. 2
Input2 priority
1.3.6.1.4.1.34093.1.2.63 2.0
get/set
1... 8
e.g. 3
Input3 priority
1.3.6.1.4.1.34093.1.2.63.3.0
get/set
1... 8
e.g. 8
Input4 priority
1.3.6.1.4.1.34093.1.2.63.4.0
get/set
1... 8
e.g. 1
Input1 mode
1.3.6.1.4.1.34093.1.2.64.1.0
get/set
D, A
D = digital; A = analog
Input2 mode
1.3.6.1.4.1.34093.1.2.64.2.0
get/set
D, A
D = digital; A = analog
Input3 mode
1.3.6.1.4.1.34093.1.2.64.3.0
get/set
D, A
D = digital; A = analog
Input4 mode
1.3.6.1.4.1.34093.1.2.64.4.0
get/set
D, A
D = digital; A = analog
Digital Input1 type
1.3.6.1.4.1.34093.1.2.65.1.0
get/set
Nc, No
Nc = normally closed; No = normally open
Digital Input2 type
1.3.6.1.4.1.34093.1.2.65.2.0
get/set
Nc, No
Nc = normally closed; No = normally open
Digital Input3 type
1.3.6.1.4.1.34093.1.2.65.3.0
get/set
Nc, No
Nc = normally closed; No = normally open
Digital Input4 type
1.3.6.1.4.1.34093.1.2.65.4.0
get/set
Nc, No
Nc = normally closed; No = normally open
Digital Input1 - threshold
1.3.6.1.4.1.34093.1.2.66.1.0
get/set
1... 10000 e.g. 6000 mV
Digital Input2 - threshold
1.3.6.1.4.1.34093.1.2.66.2.0
get/set
1... 10000 e.g. 5000mV
Digital Input3 - threshold
1.3.6.1.4.1.34093.1.2.66.3.0
get/set
1... 10000 e.g. 2000mV
Digital Input4 - threshold
1.3.6.1.4.1.34093.1.2.66.4.0
get/set
1... 10000 e.g. 4000mV
Analolg Input1 - delta
1.3.6.1.4.1.34093.1.2.67.1.0
get/set
1... 10000 e.g. 200 mV
Analolg Input2 - delta
1.3.6.1.4.1.34093.1.2.67.2.0
get/set
1... 10000 e.g. 300 mV
Analolg Input3 - delta
1.3.6.1.4.1.34093.1.2.67.3.0
get/set
1... 10000 e.g. 250 mV
Analolg Input4 - delta
1.3.6.1.4.1.34093.1.2.67.4.0
get/set
1... 10000 e.g. 360 mV
Содержание ELAN3-SNMP
Страница 1: ...ELAN3 SNMP SNMP ETHERNET CONTROLLER...
Страница 18: ...MadeintheEuropeanUnion www eldes lt...