ELAN3
SNMP Ethernet Controller
Type
•
No
– Sets input type as normally-open. Connecting the circuit leads to input violation. Default parameter.
•
Nc
– Sets input type as normally-closed. Disconnecting the circuit leads to input violation.
Threshold
– Sets the voltage value (mV) for Digital input mode. The device considers the input violated/restored once this value is
exceeded. Value range is
0... 10000 m
V. Default value is
5000 mV
.
Delta
– Sets the voltage value (mV) for Analog input mode. The device will indicate the voltage once it increases or decreases by this
value. Value range is
0... 10000 mV
. Default value is
1000 mV
.
Input name
– Title of the input that will be included in the trap message.
State ON name
– Title of the violated input state that will be included in the trap message.
State OFF name
– Title of the restored input state that will be included in the trap message.
Priority
– Priority level for setting a unique identification number for trap message related with a certain input. Value range is
1... 8
.
ATTENTION:
In order to receive the trap message regarding the voltage change on the inputs, SNMP must be enabled. For more details on
how to enable SNMP, please refer to
5.1.4. SNMP.
.
For more details on input wiring, please refer to general wiring diagram provided in
2.3. Wiring Diagrams.
5.1.6. Temperature Sensors
This section is intended for temperature sensor configuraiton.
The ELAN3-SNMP device may be equipped with up to 8 temperature sensors intended for temperature measurement in the surrounding
areas. This feature allows to monitor the temperature of up to 8 different areas in real-time in ELAN Configuration Web Server’s section
Monitoring (see
5.1.8. Monitoring
) and receive a trap message to up to 3 trap destination IP addresses (see
5.1.4. SNMP
) when the set
temperature thresholds, identified as Min Value and Max Value, are exceeded.
Adding, removing temperature sensors
To add a temperature sensor to the device, proceed as follows:
a) Power down ELAN3-SNMP.
b) Wire up the temperature sensor to the 1-Wire interface terminals (see
2.3. Wiring Diagrams
).
c) If more than one temperature sensor is required, wire another sensor in parallel to the previous one.
d) Add as many temperature sensors as necessary – wire up one after another in parallel – until the number of 8 sensors is reached.
e) Power up ELAN3-SNMP.
To view the real-time temperature values measured by each temperature sensor, please refer to section Monitoring (see
5.1.8. Monitoring
).
Temperature trap message
The device supports a trap message, which is automatically delivered to the preset destination IP adress (-es) if the minimum (Min Value)
(by default, 10 °C) or maximum (Max Value) (by default, 25 °C) temperature threshold of the temperature sensor is exceeded.
Optionally, a name for a temperature sensor can be set that will be included in the trap message when delivered to the destination IP
address (-es). This feature allows easier identification of the temperature sensor.
ATTENTION:
In order to receive the trap message regarding the voltage change on the inputs, SNMP must be enabled. For more details on
how to enable SNMP, please refer to
5.1.4. SNMP.
.
NOTE:
When multiple temperature sensors are connected, please touch and hold the sensor with your fingers and watch the temperature
value change to identify the number of the temperature sensor slot..
11