Eldes ELAN3-SNMP Скачать руководство пользователя страница 12

12

12

EN

ELAN3  

SNMP Ethernet Controller

Type
• 

No

 – Sets input type as normally-open. Connecting the circuit leads to input violation. Default parameter.

• 

Nc 

– Sets input type as normally-closed. Disconnecting the circuit leads to input violation.

Threshold

 – Sets the voltage value (mV) for Digital input mode. The device considers the input violated/restored once this value is 

exceeded. Value range is 

0... 10000 m

V. Default value is 

5000 mV

.

Delta

 – Sets the voltage value (mV) for Analog input mode. The device will indicate the voltage once it increases or decreases by this 

value. Value range is 

0... 10000 mV

. Default value is

 1000 mV

.

Input name

 – Title of the input that will be included in the trap message.

State ON name

 – Title of the violated input state that will be included in the trap message.

State OFF name

 – Title of the restored input state that will be included in the trap message.

Priority

 – Priority level for setting a unique identification number for trap message related with a certain input. Value range is 

1... 8

.

ATTENTION:

  In order to receive the trap message regarding the voltage change on the inputs, SNMP must be enabled. For more details on 

how to enable SNMP, please refer to 

5.1.4. SNMP.

.

For more details on input wiring, please refer to general wiring diagram provided in 

2.3. Wiring Diagrams.

5.1.6.  Temperature Sensors

This section is intended for temperature sensor configuraiton.
The ELAN3-SNMP device may be equipped with up to 8 temperature sensors intended for temperature measurement in the surrounding 

areas. This feature allows to monitor the temperature of up to 8 different areas in real-time in ELAN Configuration Web Server’s section 

Monitoring (see

 5.1.8. Monitoring

) and receive a trap message to up to 3 trap destination IP addresses (see 

5.1.4. SNMP

) when the set 

temperature thresholds, identified as Min Value and Max Value, are exceeded. 

Adding, removing temperature sensors

To add a temperature sensor to the device, proceed as follows:
a) Power down ELAN3-SNMP. 
b) Wire up the temperature sensor to the 1-Wire interface terminals (see 

2.3. Wiring Diagrams

). 

c) If more than one temperature sensor is required, wire another sensor in parallel to the previous one. 
d) Add as many temperature sensors as necessary – wire up one after another in parallel – until the number of 8 sensors is reached. 
e) Power up ELAN3-SNMP.
To view the real-time temperature values measured by each temperature sensor, please refer to section Monitoring (see 

5.1.8. Monitoring

).

Temperature trap message

The device supports a trap message, which is automatically delivered to the preset destination IP adress (-es) if the minimum (Min Value) 

(by default, 10 °C) or maximum (Max Value) (by default, 25 °C) temperature threshold of the temperature sensor is exceeded. 
Optionally, a name for a temperature sensor can be set that will be included in the trap message when delivered to the destination IP 

address (-es). This feature allows easier identification of the temperature sensor.

ATTENTION:

  In order to receive the trap message regarding the voltage change on the inputs, SNMP must be enabled. For more details on 

how to enable SNMP, please refer to 

5.1.4. SNMP.

.

NOTE:

   When multiple temperature sensors are connected, please touch and hold the sensor with your fingers and watch the temperature 

value change to identify the number of the temperature sensor slot..

11

Содержание ELAN3-SNMP

Страница 1: ...ELAN3 SNMP SNMP ETHERNET CONTROLLER...

Страница 2: ...SB cable Null PE ELAN3 AC DC Disconnect the mains power before installing Never install or carry out maintenance during stormy weather The electric socket that powers the device must be easily accessi...

Страница 3: ...onnector Functionality 6 2 3 Wiring Diagrams 7 3 INSTALLATION 8 4 GENERAL OPERATIONAL DESCRIPTION 9 5 CONFIGURATION CONTROL AND MONITORING METHODS 9 5 1 Web Browser 9 The following section is intended...

Страница 4: ...d following all guidelines outlined in this manual and in accordance with the operat ing conditions specified The warranty is void if the device has been exposed to mechanical impact chemicals high hu...

Страница 5: ...n collector output or 3 inputs and 2 open collector outputs Inputs customizable as NC or NO Supported input modes digital or analog 1 Wire interface for up to 8 temperature sensor connection intended...

Страница 6: ...toring default parameters STATUS Red light emitting diode indicating micro controller status F1 miniSMDC 0 5A fuse AC DC Power supply terminals C1 Open collector output terminal COM Common terminal C2...

Страница 7: ...ng 2 12V 0 10V 0 10V AC DC C1 COM Z2 Z1 5V DATA Z3 C2 Z4 Temperature sensor wiring 5V 5V DATA DATA GND GND FRONT AC DC C1 COM Z2 Z1 5V DATA Z3 C2 Z4 3 Example of output wiring 4 Alarm system or other...

Страница 8: ...le indicator LAN yellow will be steady ON indicating successful Ethernet connection see Fig No 1 6 Once the device is up and running it will automatically obtain a local IP address from the DHCP serve...

Страница 9: ...ation Web Server is username password protected By default the login details are the following User name 1234 password 1234 5 1 1 Network This section is intended for network configuration In order to...

Страница 10: ...n Web Server Default password is 1234 Retype password Repeat the password for confirmation when changing it 5 1 3 Statistics This section provides the information regarding the established TCP connect...

Страница 11: ...Default value is 0 0 0 0 Trap destination3 IP address of the 3rd trap message destination Default value is 0 0 0 0 SNMP Simple Network Management Protocol OFF SNMP enabled Default parameter ON SNMP di...

Страница 12: ...re of up to 8 different areas in real time in ELAN Configuration Web Server s section Monitoring see 5 1 8 Monitoring and receive a trap message to up to 3 trap destination IP addresses see 5 1 4 SNMP...

Страница 13: ...uipped with 2 open collector outputs C1 and C2 designed for electricalal appliance connection Nor mally outputs can be used to open close garage doors activate lights heating watering and much more Wh...

Страница 14: ...ported parameters OIDs actions available for each parameter which can be configured via SNMP as well as value range and an example comment Please note that the tables reflect the parameters described...

Страница 15: ...estored Input2 state OFF name 1 3 6 1 4 1 34093 1 2 62 2 0 get set text e g Input 2 is restored Input3 state OFF name 1 3 6 1 4 1 34093 1 2 62 3 0 get set text e g Input 3 is restored Input4 state OFF...

Страница 16: ...C1 control 1 3 6 1 4 1 34093 1 2 200 1 0 get set 0 1 0 turn OFF output 1 turn ON output Output C2 control 1 3 6 1 4 1 34093 1 2 200 2 0 get set 0 1 0 turn OFF output 1 turn ON output 5 2 7 Monitoring...

Страница 17: ...ase contact your local distributor More up to date information about your device and other products can be found at the manufacturer s website www eldes lt 6 2 Restoring Default Parameters 1 Power dow...

Страница 18: ...MadeintheEuropeanUnion www eldes lt...

Отзывы: