ELCOS SRL
- Parma - CAM-432 - MAN - EN
8
Increases Decreases
Press to set the clock.
Increases Decreases
Press, when the number flashes
Increases Decreases
Press, when the number flashes
Press to
display
Press to
display
Press to
display
Press and
wait until
OK is written
Press and
wait until
OK is written
Move DIP
switch 10 to ON
Move DIP
switch 10 to ON
Move DIP
switch 10 to OFF
Move DIP
switch 10 to OFF
Example: starts at 12:15 hrs
stops at 15:20 hrs
Example: stays locked from 23:00 hrs
unlocked at 07:30 hrs
MAINS AND GENERATOR VOLTMETER RELAYS
CLOCK PROGRAMMING
INSIDE THE CONTROL UNIT
MAINS RELAY
GENERATOR RELAY
These control the voltages of the mains and of the generator set. They intervene in the event of voltage
failure, undervoltage and overvoltage.
When voltage in three phases is detected, , with value within the preset limits, after the mains
ACCEPPTANCE DELAY (programmed to 40 sec.) the generator set stops.
(for the starting and stopping procedures see automatic operation on page 3 ).
When voltages in the two phases of the running generator set are detected with values within the preset
limits, after the GENERATOR CONNECTION TO POWER USERS delay (programmed to 7 sec.) the generator
contactor is closed. When the voltage drops, so coming out of the range of normality, the generator con
-
tactor becomes de-energized.
TO PROGRAMME SELECT THE OFF FUNCTION
CLOCK. Allows generator set operation or stopping to be programmed.
Switching off the power supply (1+ 2-) to the control unit will zero the clock.
STARTING CONSENT. Operation obtained as during mains failure
STOP. Stops starting or running of generator set
CLOCK
CLOCK
ON
ON
ON
ON