OPERATION

The control panel commands are enabled.
Starting with key 

  stopping with key 

   .

CONTROL FOR MAINS-GENERATOR CONTACTORS 
It is left to the  key 

.

By pressing on the key, the load is switched from the mains to the generator and vice versa.

PROTECTIONS

The generator set protection function in manual mode can be programmed in two ways:

· Display only of the fault that has intervened WITHOUT STOPPING the engine. The generator overfrequency fault is 

programmed with stopping of the engine. It cannot be programmed without stopping of the engine.
· Display of the fault that has intervened WITH ENGINE STOPPING. (The control panel is programmed in 

this way).

When a fault occurs on the mains, (detected by the internal oltmetric relay, or by the external call), once 

the 2 seconds have elapsed, the control unit commands the opening of the mains contactor control, and 

starts the generator set. With engine running and generator voltage normal and once the GENERATOR  TO 

POWER USERS CONNECTION DELAY has elapsed (programmed to 7 sec.) the generator contactor closes. 

While it is running the generator set is protected from possible faults. When the mains voltage is restored 

and the MAINS ACCEPTANCE time has elapsed (programmed to 40 sec.), the mains contactor closes (after 

the GENERATOR-MAINS INTERLOCK time, programmed to 1,5 sec. not adjustable). 

The COOLING TIME (programmed to 120 sec.) then allows the engine to be cooled easily before it is stop

-

ped.

Press button 

  until the warning led 

  comes on.

The engine cannot be started in any way and, if  running the engine is stopped without carrying out engi

-

ne cooling. The mains contactor stays closed. The LEDs and the instruments are active.

On pressing key 

 up the lighting 

   ,  we obtain the engine startup cycle as in automatic, 

and the power users remain supplied by the mains. If a mains fault occurs during the test, the power unit 

remains in test mode, positions itself as in automatic operation and commands the closing of the genera

-

tor contactor.

ENABLED WITH POWER UNIT IN AUTOMATIC OR TEST MODE is indicated by the display 

 

 .                        

If the relative switch is positioned on TEST ENGAGED the general alarm is activated intermittently (for 8 

sec.). When the general alarm is deactivated, and after a pause of 3 seconds, the engine starts and conti

-

nues to run for 3 minutes.

This test will be repeated automatically every week on the exact day and at the hour to which the

TEST ENGAGED switch has been positioned. 

STOPPING OF ENGINE DURING THE TEST

Press button 

  and move to function 

 .

 

UPDATING OF THE HOUR LEAVING THE SWITCH ON TEST ENGAGED

Keep pressed at the same time keys  

 and  

 until the icon TEST  

  starts to flash. 

Press key 

  within 3 sec.. 

The weekly test cycle is therefore obtained as if the relative switch had been repositioned.

 FUNCTIONS SELECTION

AUTOMATIC

OFF

TEST

WEEKLY SELFTEST

MANUAL

The function selected using the 

button is shown on the display.

Содержание CAM-432

Страница 1: ...ast 100 anomalies automatic battery charger 1A serial port RS232 This carries out the control and command function of a generator set maintains the charge of the starter battery and operates the contactors of the mains and of the generator so that power can be supplied to the power users It is constructed solely for built in installation on an electric switchboard and to be connected to other comp...

Страница 2: ...ATING MODE FLASHES WHEN ENGINE OVERLOAD IS TRIGGERED PRESS TO SHOW THE INSTRUMENTS AVAILABLE FAULT STOPPING DUE TO OVERFREQUENCY MAINS VOLTAGE IS PRESENT MAINS IS CONNECTED TO THE USER GENERATOR IS PLUGGED TO THE USER GENERATOR VOLTAGE IS PRESENT PRESS TO SELECT THE FUNCTIONS OF AUT OFF MAN TEST THE ENGINE IS RUNNING STOPPING DUE TO ENGINE OVERHEATING STOPPING DUE TO INSUFFICIENT OIL PRESSURE KEY ...

Страница 3: ...adjustable The COOLING TIME programmed to 120 sec then allows the engine to be cooled easily before it is stop ped Press button until the warning led comes on The engine cannot be started in any way and if running the engine is stopped without carrying out engi ne cooling The mains contactor stays closed The LEDs and the instruments are active On pressing key up the lighting we obtain the engine s...

Страница 4: ...e P1 of the voltage and frequency of the battery charger alter nator PERMANENT MAGNETS or PRE EXCITATION and from the frequency and residual voltage of the generator When detection has been made it disconnects the starter motor and lights the LED By pressing the key the protection devices and all the stopped functions are re activated Blocks the start cycle if the motor is not started after the wh...

Страница 5: ...HOUR METER The emergency stop can be activated in all working conditions by mounting one or more click down push button The stop is immediate without engine cooling enables the general alarm and is shown on the display Do not use the emergency push button linked to a stop system that is not energized when the unit is running EMERGENCY STOP REMOTE CONTROLS START OR TEST STOP EMERGENCY EJP FUNCTION ...

Страница 6: ...mer ENGINE TYPE STOP SYSTEM SELEC TION WEEKLY SELF TEST GENERA TOR FRE QUENCY MAINS AND GENERA TOR VOLTAGE Connect the jumper 5E 6E if the emergency button is not fitted 1 5mm MIN 5m MAX Colour bridge Black When you connect terminal remove the BLACK bridge MAINS DETECTION Colour bridge Red Remove to deactivate the internal mains detection ENGINE RUNNING DETECTION NEVER INSTALL THE EMERGENCY PUSH B...

Страница 7: ...See CHOOSING THE NUMBER OF AMMETERS on page 8 of the PROG manual ENGINE RUNNING THRESHOLD ADJUSTMENT Adjustment is not normally neces sary If it is necessary perform the following opera tions Start the engine manually and bring it down to minimum speed Turn the potentiometer anti clockwise until the indicator lights up TEST REMOTE CONTROLS 50m max CALL STARTING Shown by the START on the display 1 ...

Страница 8: ...oltage failure undervoltage and overvoltage When voltage in three phases is detected with value within the preset limits after the mains ACCEPPTANCE DELAY programmed to 40 sec the generator set stops for the starting and stopping procedures see automatic operation on page 3 When voltages in the two phases of the running generator set are detected with values within the preset limits after the GENE...

Страница 9: ...ELCOS SRL Parma CAM 432 MAN EN 9 REMARKS ...

Страница 10: ...ELCOS SRL Parma CAM 432 MAN EN 10 REMARKS ...

Страница 11: ... stressing the electronic board Do not allow pieces of copper wire or other metal residues to fall onto the control unit Never disconnect the battery terminals with the engine running Strictly avoid using a battery charger for emergency starting the control unit may get damaged To protect the safety of people and equipment disconnect the terminals of the electrical system from the battery poles be...

Страница 12: ...range 50 253Vac Generator ammeter Max 1000A precision 2 operating range 0 02 20ma 6A Frequency meter Precision 0 1 Hz frequency range 45 85Hz Hour meter 4 digits Degree of protection Front panel IP 64 Rear panel IP00 Temperature range 20 50 º C Dimensions LxHxP mm 243x170x62 Hole mm 227x155 Weight 710g DECLARATION OF CONFORMITY We ELCOS s r l declare under our sole responsibility that the control ...

Отзывы: