Assembly
Electrical installation
General information
Electrical installation and connection
work must only be performed by an
electrician. The VDE/ÖVE/Sev and
EVU provisions and conditions must
be observed.
Mains connection and connection
from building wires
The device is designed for permanent
connection and connection wires NYM
3 x 1.5 mm
2
or H05W-F 3 x 1 mm
2
.
Burner and switch field are wired.
The mains connection is with a clamp
(3) on the device via a power circuit
envisaged and secured for this.
It must be possible to separate the
burner from the network by suitable
means. Allpolar switches with a
contact opening width > 3 mm or power
protector switch can be used for this.
Mains voltage:
230 V, 50 Hz
Mains connection fuse:
10 A
Power consumption:
max. 420 W
Wastewater pump power consumption
Max. switched current KM628
1A / relay
Max. 2.5 A total
The switch field (1) can be folded up
after the securing screw (2) has been
removed.