Assembly
Burner connection, filling the system
Siphon and condensation trap
x
Dismantle the siphon (1), fill and
reassemble
x
Connect the condensation trap or
neutralisation
equipment
(accessory)
with
the
siphon
Note
The condensation pipe (2) must not be
securely connected to the wastewater
pipe. The condensation must be able
to be drip freely into a funnel.
Filling the system
x
Connect the water pipe to the KFE
tap
(in
the
building)
x
Open all radiator valves
x
Fill cold system to 1 bar
x
Check water quality
x
Vent pump (if necessary, loosen
blade wheel with screwdriver)
x
Fill condensation siphon with water
(approx. 05. l)
x
Run pump several times
x
After complete venting, fill system
to the final operating pressure
x
Close venting screw and remove
filler
pipe
Replacement system
x
Carefully rinse system
x
Check seal at connection points
x
Carefully vent system
1 Siphon
2 Condensation
connection
3
Cable insert, external cabling
4
Gas connection ¾
5 Lead
connection
6 Reflux
connection
The connection is only performed
by an authorised expert.
x
Connect the gas pipe
x
Check seal of pipes
x
Connect required exhaust closing
plate (concentric / parallel)
x
Insert boiler connector (concentric
or parallel) from above into the
respective opening and press into
the socket. To do this, use the
lubricant suitable for PPS exhaust
pipes
x
Connect exhaust collector to the
exhaust
system
x
Assemble supports
1
2
5 1 4 2 6
3
15