SET GENERAL PARAMETER (SET UP)
Entry to menu:
seT UP
Æ
seT Up
RESET
SET DO1
SET DO2
SET HR_
ELM-961
instruction manual
IM441-U v0.6
pag. 6
DO_ OFF OFF
SET CT
Increase
Set CT ratio
from 1 to 2000
Decrease
SET VT
Increase
Set VT ratio
from 0.1 to 400.0
Decrease
seT AV9 T
Increase
Set average time
from 1 to 30 minutes
Decrease
seT EN
TOT PAR
Set Energy visualization
NORMAL
type
seT 3pH BALANC
Set connection UN_BAL
Type 1PH L3
seT MDE
-3-
Set wiring connection
type
-4-
seT SYN MDE
L3
Set synchronism
50
type
60
seT PUL SE
Set pulse weight
10.0 kW-kVAr / pulse
(version with digital output)
01.0 kW-kVAr / pulse
0.10 kW-kVAr / pulse
0.01 kW-kVAr / pulse
seT TPL
Increase
from 100 to 500 mS
in step by 100 mS
Decrease
(version with digital output)
seT ID ADR
Increase
Set address of network
from 001 to 127
Decrease
(version with serial output)
seT SER BDR
Set baud rate
19200 baud
19.2
serial interface
9600 baud
9.60
(version
with serial output
)
4800 baud
4.80
2400 baud
2.40
seT PAR
Set parameters of bit: 8data 1stop-no parity 8.1 pAR NO
Comunication
bit: 8data 2stop-no parity 8.2 paR NO
serial interface bit: 8data 1stop-even parity 8.1 paR eVe
(version with serial output)
bit: 8data 1stop-odd parity
8.1 paR ODD
SET PAS
Increase
Set Password
OFF - 0002 ÷ 9999
Decrease
Confirm and end of general settings