background image

MEASURES VISUALIZATION 

ELM-961 

 

instruction manual

IM441-U v0.6 

pag. 12

 

The instrument is divided in two distinct section: 
the first is composed by three displays (F), by A and B keys and by LED bar 
D; the second (in the low part) is composed by G display, by C key and by 
LED bar E. 
The two sections are to consider as two different instruments in a only one 

 

 

box, in fact it’s possible to act in a zone without to modify the visualization in 
the other (peak value and energy counters visualization excluded). 

 

Visualization section  1 

h

 

 

 

 

The  three  measures  of  phases  (on  L1,  L2  and  L3),  of  the  parameter 
indicated from the led D on, appears on F display. For the measure of the 
phase to phase voltages (V 

L-L

), the three measures are V

L1-L2

, V

L2-L3

, V

L3-L1

   

V

L-N 

V

L-L   

Hz    °C

 

It’s necessary to press the B button to select the parameter that can be displayed and indicated from D LED. 
Press A button to see on F display the three phase value (the average of the single phase of voltage, current, power 
factor and the sum of single phase for the power) of the parameter selected: the led inside the A key is on. 
To press another time the same key the visualization come back at the phase values. 
The unit of measurement can be expressed in kilo or Mega, in the this case the relative LED is on. 
A sign – on the first digit indicates the visualization of the capacitive power factor (example the reading -.95 indicates a 
power factor of 0.95 capacitive) 
Note: If in the Setup the single phase mode (1PH   L3) is set, all the measures appear on the L3 display. 

 

Visualization section  2 
At the same way of the section 1, press the C button to select the parameter that can be displayed and indicated from E 
LED. The voltage values are of the three phase system, the frequency is of the L3 channel. 

 

Visualization energy and hours counters 
With the C key it’s possible to visualize on F display the active, reactive and apparent energy counters. One segment of 
the right digit of the G display, in correspondence of the kWh and KVArh  on the front panel, turn on, to indicate the 
visualization of the active and reactive energy counters. The led VA and the segment of the right digit of the G display, in 
correspondence of …h on the front panel, turn on, to indicate the visualization of the apparent energy counter. To 
complete the visualization the led k over the F display could be on. 
This is the visualization if NORMAL  is the set in EN  voice of the setup. Instead if the setting is TOT   PAR  on the F 
display will be visualized alternatively the partial and the total active, reactive and apparent energy counters; the first digit 
of the G display indicates the type of the counter: P  for the partial (the user could be reset it) and T for the total (it’s no 
possible to reset it). 

 

The right digit of G display, in correspondence of the …h, turn on, when the visualization of hours counters is active. 

 

The reading of the counters use the 9 digits (maximum reading 99999999.9) of the F display: the measure is displayed in 
the way that the L1 display will indicate the first 3 digits, the display L2 the seconds 3 digits and the L3 display the last 3. 
For example if: L1=000, L2=028, L3=53.2 the reading is 2853.2 kWh. 

Содержание ELM-961

Страница 1: ...internal CT digital output in alternative to the serial port serial port in alternative to the digital output power supply different from standard version current input 1A MEASURED PARAMETERS paramete...

Страница 2: ...400V 300 500V phase to phase 175 290V phase neutral 230V 175 290V phase to phase 130 170V phase neutral L2 L3 phase to phase power supply 110V 85 145V phase to phase 50 85V phase neutral 230V 300 500V...

Страница 3: ...IRES ELM on line with 3 wires without neutral or with neutral not supplied the N terminal must not be connected L1 S1 P1 S1 L2 P1 L3 N S1 S2 P1 P2 LOAD I1 I3 VL1 VL2 VL3 INSERTION ON THREE PHASE LINE...

Страница 4: ...N ON SINGLE PHASE LINE I1 I2 S1 I3 VL1 VL2 VL3 if the multimeters are used on single phase line the measure are referred at the L3 phase The others data displayed relatives at value of three phase sys...

Страница 5: ...the values of the active reactive and apparent energy counters If it s selected with the A and B keys the display indicates the maximum and average values G display for the visualization of the electr...

Страница 6: ...kVAr pulse version with digital output 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with digital output seT ID ADR In...

Страница 7: ...decrease it press the C key To confirm it press the A key The average time is the time used to calculate the average parameters avg and the maximum demand maxD Programming of the energy visualization...

Страница 8: ...rd when required by the instrument at the enter of the setup use the A B and C keys as the same way done previously The menu is cyclic After the last setting the instrument go back to the first page o...

Страница 9: ...ALR LO With ALR SYS 123 the digital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of t...

Страница 10: ...the set SET THE HIGH AND THE LOW THRESHOLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with...

Страница 11: ...ime the B key to select the parameter and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I...

Страница 12: ...all the measures appear on the L3 display Visualization section 2 At the same way of the section 1 press the C button to select the parameter that can be displayed and indicated from E LED The voltag...

Страница 13: ...s max maxD avg I L1 max avg I L2 max avg I L3 max avg phase currents maximum of average phase currents max demand max maxD avg W max avg VAr max avg VA max avg three phase power maximum of average thr...

Страница 14: ...se speed Not shielded connection As shown in the diagram it is necessary to place a serial RS232 485 converter between the RS232 PC s outlet and the instrument s it s necessary to insert a line termin...

Страница 15: ...ELM 961 instruction manual IM441 U v0 6 pag 15 DIMENSIONS ELM 961 96 9 56 cut panel 96 96 R3 92 90 92 20...

Страница 16: ...1 to 400 0 current inputs from 0 02 to 5A permanent overload 30 from external TA with secondary 5A primary programmable from 5 to 10000A auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outpu...

Отзывы: