background image

N.

Paramet

er

Descritton

Default

Fir the 

ierr

 alarm functin, this 

parameter has ni meaning.

17

blal

Blicking Alarm. This functin 

blicks the alarms.

YES

 - enables inital blicking 

 

NO

- inhibits inital blicking

 

ni

18

xyal

Hysteresis if Alarm. Defnes the 

diference between the value if 

PV at which the alarm is triggered

and the value at which it is 

turned if.

0.0

Calibraton level

19

pass

Passwird. This parameter is 

presented befire the pritected 

levels. See item Pritectin if 

Cinfguratin.

0

20

(al

Calibratin. Enables the 

pissibility fir calibratin if the 

indicatir. When the calibratin is 

nit enabled, the related 

parameters are hidden.

ni

21

inL(

Input Liw Calibratin. Enter the 

value cirrespinding ti the liw 

scale signal applied ti the analig 

input.

22

ink(

Input High Calibratin. Enter the 

value cirrespinding ti the full 

scale signal applied ti the analig 

input.

23

rstr

Restire. Restires the factiry 

calibratin fir all inputs and 

iutputs, disregarding 

midifcatins carried iut by the 

user.

24

Pas.(

Passwird Change. Alliws defning

a new access passwird, always 

diferent frim zeri.

0

25

Prot

Pritectin. Sets up the Level if 

Pritectin. See 

Table 3 - 

. 

1

All   types   if   input   are   calibrated   in   the   factiry.   In   case   a

recalibratin is required; it shall be carried iut by a specialized

prifessiinal. In case this level is accidentally accessed, di nit

perfirm alteratin in its parameters.

6.2

CONFIGURATION PROTECTION

The   cintriller  privides  means  fir  pritectng  the   parameters

cinfguratins,   nit   alliwing   midifcatins   ti   the   parameters

values,   aviiding   tampering   ir   impriper   manipulatin.   The

parameter  

Protecton

  (

PROt

),   in   the   Calibratin   level,

determines   the   pritectin   strategy,   limitng   the   access   ti

partcular levels, as shiwn by the 

Table 3 - .

PROTECTION

LEVEL

PROTECTION LEVELS 

1

Only the Calibratin level is pritected.

2

Calibratin and Input levels. 

3

Calibratin, Input and Tuning levels.

4

All levels are pritected, including SP.

Table 3 - Protecton levels for the configuraton

6.2.1

ACCESS PASSWORD

The   pritected   levels,   when   accessed,   request   the   user   ti

privide the 

Access Password

 fir grantng permissiin ti change

the cinfguratin if the parameters in these levels.

The primpt  

PASS

  precedes the parameters in the pritected

levels.   If   ni   passwird   is   entered,   the   parameters   if   the

pritected levels can inly be visualized.

The Access Passwird is defned by the user in the parameter

Password Change

 (

PAS.(

), present in the Calibratin Level. 

The

factory default for the tassword code is 1111

6.2.2

PROTECTION ACCESS PASSWORD

The  pritectin  system  built   inti   the  cintriller  blicks  fir  10

minutes the access ti pritected parameters ater 5 cinsecutve

frustrated attempts if guessing the cirrect passwird.

6.2.3

MASTER PASSWORD

The Master Passwird is intended fir alliwing the user ti defne

a new passwird in the event if it being firgitten. The Master

Passwird diesn’t grant access ti all parameters, inly ti the

Password  Change

  parameter (

PAS(

).  Ater  defning  the  new

passwird,   the   pritected   parameters   may   be   accessed   (and

midifed) using this new passwird.

The master passwird is made up by the last three digits if the

serial number if the cintriller 

added

  ti the number 9000. As

an example, fir the equipment with serial number 07154321,

the master passwird is 9 3 2 1. 

Cintriller   serial   number   is   displayed   by   pressing  

 

  fir   3

secinds.

6.3

DETERMINATION OF PID PARAMETERS

During   the   pricess   if   determining   autimatcally   the   PID

parameters,   the   system   is   cintrilled   in  

ON:OFF

  in   the

prigrammed Setpiint. The auti-tuning pricess may take several

minutes ti be cimpleted, depending in the system. The steps

fir executng the PID auti-tuning are:

Select the pricess Setpiint.

Enable auti-tuning at the parameter “

Atvn

”, selectng

FAST

 

ir

 

FULL

.

The iptin 

FAST

 

perfirms the tuning in the minimum pissible

tme, while the iptin  

FULL

 gives priirity ti accuracy iver the

speed.

The sign TUNE remains lit during the while tuning phase. The

user must wait fir the tuning ti be cimpleted befire using the

cintriller.

During auti tuning periid the cintriller will impise iscillatins

ti  the   pricess. PV will  iscillate  ariund  the  prigrammed  set

piint and cintriller iutput will switch in and if many tmes.

If the tuning dies nit result in a satsfactiry cintril, refer ti

Table 4 - 

 fir guidelines in hiw ti cirrect the behaviir if the

pricess.

PARAMETER

VERIFIED PROBLEM

SOLUTION

Band Pripirtinal

Sliw answer

Decrease

Great iscillatin

Increase

Rate Integratin

Sliw answer

Increase

Great iscillatin

Decrease

Derivatve Time

Sliw answer ir 

instability

Decrease

Great iscillatin

Increase

Table 4 - Guidance for manual adjustment of the PID

parameters

7

MAINTENANCE

7.1

PROBLEMS WITH THE CONTROLLER

Cinnectin errirs and inadequate prigramming are the mist

cimmin errirs fiund during the cintriller iperatin. A fnal

revisiin may aviid liss if tme and damages.

The cintriller displays sime messages ti help the user identfy

priblems.

User manual - Thermocontroller ELK4C

Page 5/6