Message
Descritton of the Problem
----
Open input. Ni sensir ir signal.
Err1
Err6
Cinnectin and/oir cinfguratin priblems.
Check the wiring and the cinfguratin.
Other errir messages may indicate hardware priblems requiring
maintenance service.
7.2
PROCESS VARIABLE INPUT CALIBRATION
All inputs are factiry calibrated and recalibratin shiuld inly be
dine by qualifed persinnel. If yiu are nit familiar with these
pricedures di nit attempt ti calibrate this instrument.
a- Set the type parameter accirding ti the input
type
.
b- Cinfgure the liwer and upper limits if indicatin fir
the maximum span if the selected input type.
c- Access the calibratin level.
d- Enter the passwird.
e- Enable the calibratin setng YES in the parameter
(Alib
.
f- With the aid if an electrical signals simulatir, apply a
signal level clise the liwer limit if the measuring range
if the input, in the cirrespinding terminals.
g- Access the parameter “
inLC
”. With the keys
and
adjust the display reading such as ti match the applied
signal. Then press the
P
key.
h- Inject a signal that cirrespinds ti a value a little liwer
than the upper limit if indicatin.
i- Access the parameter “
ink(
”. With the keys “
” and “
”, adjust the display reading such as ti match the
applied signal. Then press the key “
P
” untl return ti
the Display PV screen.
j- Validate the calibratin perfirmed.
Notep
When checking the cintriller calibratin with a Pt100
simulatir, pay attentin ti the simulatir minimum excitatin
current requirement, which may nit be cimpatble with the
0.170 mA excitatin current privided by the cintriller.
8
TECHNICAL DATA
8.1
ELECTRICAL DATA
Piwer supply
100 ti 240 Vac (±10 %), 50/o60 Hz
48 ti 240 Vdc (±10 %)
Optinal 24 V
12 ti 24 Vdc /o 24 Vac
(-10 %/o+20%)
Piwer cinsumptin max.
5 VA
Input
Thermiciuples J; K; T and Pt100
(accirding ti Table 1 - )
Internal Resilutin
12000 levels (frim -1999 up ti 9999)
Rate if input reading
up ti 10 per secind (*)
Accuracy
Thermiciuples J, K, T
0.25 % if the span 1 °C (**)
Pt100
0.2 % if the span
Intut Imtedance
Pt100 and thermiciuples:
> 10 M
Ω
Measurement if Pt100
3-wire type, (α=0.00385)
With cimpensatin fir cable
length
excitatin current if 0.170 mA
OUTPUTS
OUT1
Relay SPST; 1.5 A /o 240 Vac /o 30 Vdc
OUT2
Relay SPST; 1.5 A /o 240 Vac /o 30 Vdc
(*) Value adipted when the Digital Filter parameter is set ti 0
(zeri) value. Fir Digital Filter values ither than 0, the Input
Reading Rate value is 5 samples per secind.
(**) The use if thermiciuples requires a minimum tme interval
if 15 minutes fir stabilizatin.
8.2
MECHANICAL DATA
Environmental conditons
Operatin Temperature
0 ti 50 °C
Relatve Humidity
80 % @ 30 °C
Fir temperatures abive 30 °C,
reduce 3 % fir each °C
Others
Internal use
Categiry if installatin II
Degree if pillutin 2
Alttude o 2000 meters
Dimensiins
48 x 48 x 35 mm (1/o16 DIN)
Cutiut in panel
45.5 x 45.5 mm (+0.5 -0.0 mm)
Appriximate weight (24 V /o 240 V) 60 g /o 75 g
Frint panel
IP65, Pilycarbinate (PC) UL94 V-2
Enclisure
IP20, ABS+PC UL94 V-0
Cinnectins
Specifc cinnectins fir firk
terminals
8.3
FUNCTIONAL FEATURES
E
lectrimagnetc cimpatbility
IEC 61326-1:2013 and IEC
61326-1:2012
Emissiin
CISPR11/oEN5501
Immunity
EN61000-4-2, EN61000-4-3,
EN61000-4-4, EN61000-4-5,
EN61000-4-6, and EN61000-4-
11
Safety
UL 61010-1
Prigrammable level if PWM
frim 0.5 up 100 secinds
Start-up iperatins
ater 3 secinds cinnected ti
the piwer
Certfcatin
and
9
ORDERING CODE
Piwer supply
24
12…24 Vdc /o 24Vac (-10%...+20%)
240
100…240Vac /o 48…240 Vdc (±10%)
Input
C
J, K, T, PT100
OUT 1 Output
R
Relay SPST-NO 1,5A (240Vac /o
30Vdc)
OUT 2 Output
2R
Relay SPST-NO 1,5A (240Vac /o
30Vdc)
User manual - Thermocontroller ELK4C
Page 6/6
EK4C - 24 - C - R - 2R
Thermicintriller
Piwer supply
OUT 1
Input
OUT 2