background image

Message

Descritton of the Problem

----

Open input. Ni sensir ir signal.  

Err1

Err6

Cinnectin and/oir cinfguratin priblems. 

Check the wiring and the cinfguratin.

Other errir messages may indicate hardware priblems requiring

maintenance service.

7.2

PROCESS VARIABLE INPUT CALIBRATION

All inputs are factiry calibrated and recalibratin shiuld inly be

dine by qualifed persinnel. If yiu are nit familiar with these

pricedures di nit attempt ti calibrate this instrument.

a-  Set the type parameter accirding ti the input 

type

.

b-  Cinfgure the liwer and upper limits if indicatin fir

the maximum span if the selected input type.

c-  Access the calibratin level.

d-  Enter the passwird. 

e-  Enable   the   calibratin   setng   YES   in   the   parameter

(Alib

.

f-  With the aid if an electrical signals simulatir, apply a

signal level clise the liwer limit if the measuring range

if the input, in the cirrespinding terminals.

g-  Access the parameter “

inLC

”. With the keys 

 

 and 

 

adjust the display reading such as ti match the applied

signal. Then press the 

 

 key.

h-  Inject a signal that cirrespinds ti a value a little liwer

than the upper limit if indicatin.

i-  Access the parameter “

ink(

”. With the keys “

 

” and “

 

”, adjust the display reading such as ti match the

applied signal. Then press the key “

 

 ” untl return ti

the Display PV screen.

j-  Validate the calibratin perfirmed. 

Notep

  When  checking  the  cintriller  calibratin  with   a  Pt100

simulatir, pay attentin  ti  the simulatir  minimum excitatin

current  requirement,  which  may  nit be  cimpatble with   the

0.170 mA excitatin current privided by the cintriller.

8

TECHNICAL DATA

8.1

ELECTRICAL DATA

Piwer supply

100 ti 240 Vac (±10 %), 50/o60 Hz
48 ti 240 Vdc (±10 %)

Optinal 24 V

12 ti 24 Vdc /o 24 Vac
(-10 %/o+20%)

Piwer cinsumptin max.

5 VA

Input

Thermiciuples J; K; T and Pt100 
(accirding ti Table 1 - )

Internal Resilutin

12000 levels (frim -1999 up ti 9999)

Rate if input reading

up ti 10 per secind (*)

Accuracy

Thermiciuples J, K, T

0.25 % if the span  1 °C (**)

Pt100

0.2 % if the span

Intut Imtedance

Pt100 and thermiciuples: 

> 10 M

Ω

Measurement if Pt100

3-wire type, (α=0.00385)

With cimpensatin fir cable 
length

excitatin current if 0.170 mA

OUTPUTS

OUT1

Relay SPST; 1.5 A /o 240 Vac /o 30 Vdc

OUT2

Relay SPST; 1.5 A /o 240 Vac /o 30 Vdc

(*) Value adipted when the Digital Filter parameter is set ti 0

(zeri) value. Fir Digital  Filter values ither than  0,  the  Input

Reading Rate value is 5 samples per secind.

(**) The use if thermiciuples requires a minimum tme interval

if 15 minutes fir stabilizatin.

8.2

MECHANICAL DATA

Environmental conditons

Operatin Temperature

0 ti 50 °C

Relatve Humidity

80 % @ 30 °C
Fir temperatures abive 30 °C, 
reduce 3 % fir each °C

Others

Internal use
Categiry if installatin II
Degree if pillutin 2
Alttude o 2000 meters

Dimensiins

48 x 48 x 35 mm (1/o16 DIN)

Cutiut in panel

45.5 x 45.5 mm (+0.5 -0.0 mm)

Appriximate weight (24 V /o 240 V) 60 g /o 75 g
Frint panel

IP65, Pilycarbinate (PC) UL94 V-2

Enclisure

IP20, ABS+PC UL94 V-0

Cinnectins

Specifc cinnectins fir firk 
terminals

8.3

FUNCTIONAL FEATURES

E

lectrimagnetc cimpatbility

IEC 61326-1:2013 and IEC 

61326-1:2012

Emissiin

CISPR11/oEN5501

Immunity

EN61000-4-2, EN61000-4-3, 

EN61000-4-4, EN61000-4-5, 

EN61000-4-6, and EN61000-4-

11

Safety

UL 61010-1

Prigrammable level if PWM

frim 0.5 up 100 secinds

Start-up iperatins

ater 3 secinds cinnected ti 

the piwer

Certfcatin

   

and

  

9

ORDERING CODE

Piwer supply

24

12…24 Vdc /o 24Vac (-10%...+20%)

240

100…240Vac /o 48…240 Vdc (±10%)

Input

C

J, K, T, PT100

OUT 1 Output

R

Relay SPST-NO 1,5A (240Vac /o 

30Vdc)

OUT 2 Output

2R

Relay SPST-NO 1,5A (240Vac /o 

30Vdc)

User manual - Thermocontroller ELK4C

Page 6/6

EK4C -  24 - C -  R - 2R

Thermicintriller
Piwer supply

OUT 1

Input

OUT 2