5

FUNCTIONS

5.1

INPUT TYPE SELECTION

Table 1 -  shiws the sensir types accepted and their respectve

cides and ranges. Access the parameter TYPE in the INPUT level

ti select the appripriate sensir.

TYPE

CODE

RANGE OF MEASUREMENT

Thermiciuple J

Tc j

Range: -110 ti 950 ºC (-166 ti 1742 

ºF)

Thermiciuple K

Tc k

Range: -150 ti 1370 ºC (-238 ti 2498 

ºF)

Thermiciuple T

Tc t

Range: -160 ti 400 ºC (-256 ti 752 ºF)

Pt100

Pt

Range: -200 ti 850 ºC (-328 ti 1562 

ºF)

Table 1 - Input types

The input type shiuld be the frst parameter ti be cinfgured in

the   cintriller.   Any   midifcatins   in   the   input   type   will

autimatcally change ither related parameters. The user must

verify   the   cinfguratin   every   tme   that   an   input   type

midifcatin iccurs.

5.2

OUTPUTS

The cintriller has  twi iutputs. The user can cinfgure these

iutputs ti iperate as 

Control Outtut (

(trl

)

 ir 

Alarm Outtut

(

al

)

.

OUT1

 - Output Relay SPST-NO

OUT2

 - Output Relay SPST-NO

5.2.1

CONTROL OUTPUT (

(TRL

)

The cintril strategy can be 

ON:OFF

 (when 

PB

 = 

0.0) 

ir 

PID

. The

PID parameters can be autimatcally determined enabling the

auti-tuning functin (

ATvN

).

5.2.2

ALARM OUTPUT (

AL

)

The cintriller cintains 2 alarms that can be directed (assigned)

ti any  iutput channel. The alarm  functins  are  described in

Table 2 - 

off

Output is nit used as alarm. 

lo

Alarm if Absilute 

Minimum Value. 

Triggers when the 

value if measured PV 

is 

below

 the value 

defned fir alarm 

Set 

point

 

(SPAL)

ki

Alarm if Absilute 

Maximum Value. 

Triggers when the 

value if measured PV 

is 

above

 the value 

defned fir alarm Set 

piint.

dif

Alarm if Diferental. In this functin the 

parameters, SPAL represent the deviatin if PV in 

relatin ti the SP if CONTROL

Pisitve SPAL

Negatve SPAL

difl

Alarm if Minimum Diferental Value. It triggers 

when the value if PV is 

below

 the defned piint by 

SP-SPAL

Pisitve SPAL 

Negatve SPAL 

difk

Alarm if Maximum Diferental. Triggers when the 

value if PV is 

above

 the defned piint by SP+SPAL

Pisitve SPAL 

Negatve SPAL 

ierr

Alarms if the Sensir Break (Sensir 

Break Alarm

). It

is actvated when the Input presents priblems such

as interrupted sensir, bad cinnectin, etc

Table 2 - Alarm functons

Imtortant note

: Alarms cinfgured with the 

ki

dif

, and 

difk

functins  alsi  trigger  their  assiciated   iutput   when   a  sensir

fault is identfed and signalled by the cintriller. A relay iutput,

fir example, cinfgured ti act as a High Alarm (

ki

), will iperate

when   the   SPAL value  is  exceeded   and  alsi   when   the   sensir

cinnected ti the cintriller input is briken.

5.2.3

INITIAL BLOCKING OF ALARM

The  

inital   blocking

  iptin   inhibits   the   alarm   frim   being

recignized if an alarm cinditin is present when the cintriller is

frst energized (ir ater a transitin frim run YES  

  NO). The

alarm will be enabled inly ater the iccurrence if a nin alarm

cinditiin filliwed by a new iccurrence fir the alarm.

The   inital   blicking   is   useful,   fir   instance,   when   ine   if   the

alarms  is  cinfgured   as a  minimum  value   alarm, causing  the

actvatin   if   the   alarm   siin   upin   the   pricess   start-up,   an

iccurrence that may be undesirable.

The   inital   blicking   is   disabled   fir   the   sensir   break   alarm

functin 

ierr

.

5.2.4

OFFSET

Alliws fne adjustments ti the PV reading fir cimpensatin if

sensir errir.

6

OPERATION

The cintriller’s frint panel, with its parts, can be seen in Figure 2-

Figure 2- Frint panel

Distlay of PV : Programming

 (tip display, red ciliur): Displays

the current value if PV (

Process Variable

). When in cinfguratin

mide, it shiws the parameters names.

Distlay   of   SP   :   Parameters  

(bittim   display,   green   ciliur)

p

Displays   the   value   if   SP   (

Set   point

).   When   in   cinfguratin

mide, it shiws the parameters values.

TUNE   Indicator

:   Stays   ON   while   the   cintriller   is   in   tuning

pricess.

OUT Indicator

: Fir relay ir pulse cintril iutput; it refects the

actual state if the iutput.

A1   and   A2   Indicators

:   signalize   the   iccurrence   if   alarm

situatin.

P Key

: used ti walk thriugh the menu parameters.

 

Increment key and 

 

 - Decrement key

: alliw altering the

values if the parameters.

User manual - Thermocontroller ELK4C