Configuration and programming
Logging
Individual logging for each input. Interval from 10 seconds to
1 hour Communicated and stored automatically on redundant
servers. Local buffer: 8,000 samples per channel.
Input trigger
Up to four alarms per input (all with thresholds for alarm/reset
and separate block times).
Each alarm and reset can trigger up to four separate actions
(e.g. sending messages, controlling outputs and counters).
Schedules
Up to 20 schedules (all with four intervals and flags for all days
of the week). Up to four actions for each schedule at start/end
of an interval.
Timers
Up to 20 timers (all can be set to repeat hourly, daily, weekly or
monthly). Each timer can activate up to four actions.
Server communication
Configuration
Automatic, DHCP
Host protocol
IP/UDP, proprietary encrypted payload
Port
Outbound port UDP 8844
Inbound port UDP 28672-32767 (random per session)
Encryption
128 bits (unique key for ezeio)
Traffic
Typically 5–15 MB/month (depends on usage)
Local buffer
8,000 samples per channel (non-volatile)
EN
868 – 870 MHz Transceiver, Model number: A110LR09C
(Trade name) N/A
Software version AIR FCC Test Vers. 4.3.0.0
The highest EIRP under normal and extreme environmental conditions is as follows:
Frequency Band
Mode
Output ERP
(dBm)
Output ERP
(mW)
M
GFSK
12.33
17.1
M
2-FSK
12.36
17.2
N
GFSK
12.34
17.1
N
2-FSK
12.36
17.2
P
GFSK
12.34
17.1
P
2-FSK
12.35
17.2
Q
GFSK
6.72
4.7
Q
2-FSK
6.69
4.7
R
GFSK
12.37
17.3
R
2-FSK
12.35
17.2
X
GFSK
9.69
9.3
X
4-FSK
12.08
16.1