DK50 9x4VRT/M

 

NP-DK50-9x4VRTM_ED-EN-2_10-2018                                                   - 34 -  

10/2018

 

18.2.  Functionality check 

  Check  air  pump  condition  –  the  air 

pumps  should  be  operating  normally 
without  excessive  vibration  or  noise. 
Troubleshoot  any  problem  or  call  in 
service personnel if trouble is detected. 

  Check fan operation (visually) – the fans 

must  be running  per  the  description  of 
their function. Troubleshoot any problem 
or  call  in  service  personnel  if  trouble  is 
detected. 

  Check  to  ensure  the  power  cord,  the 

cable for the pressure sensor on the air 
tank and the connecting compressed air 
hoses 

are 

undamaged. 

Replace 

damaged  components  or  call  in  service 
personnel. 

  Check  the  ambient  temperature  on  the 

display – the ambient temperature must 
be  below  the  temperature  limit  (40

o

C). 

Cool  the  space  if  the  temperature  is 
high. 

  Check  for  alarm  conditions  on  the 

display  –  troubleshoot  and  remedy  all 
alarms. 

 

18.3.  Leak  check  compressed  air 

connections  and  inspect  the 
equipment 

Leak testing: 

  Leak test the compressor’s compressed 

air  lines  when  running  –  when  the 
compressor  is  delivering  pressure  (not 
during regeneration blowdown). 

  Use  a  leak  analyser  or  soapy  water  to 

check  all  joints  and  connections  for 
leaks.  Tighten  or  reseal  the  connection 
where leaks are found

.

 

 

Inspecting the equipment: 

  Check  the  condition  of  the  compressor 

air pump for normal operation and noise 
levels. 

  Check the operation of fans. 

  Check the condition of filters.  

  Check  the  condition  of  the  air  pump 

itself: 

 -  contamination  in  the  crankcase  and 
play in the crankshaft  

  Replace any parts as needed. 

 

18.4.   Inspection of electrical 

connections 

 

Inspect  the  product’s  electrical 
connections  when  the  mains  are 
disconnected! 

 

Inspection  

  Check  the  mechanical  function  of  the 

main switch Q10 and the START-STOP 
buttons, S1 and S2. 

  Check  the  power  cord,  conductors 

connected  to  the  X1  terminal  strip  and 
the  main  switch  to  ensure  they  are 
undamaged.  Inspect  to  ensure  the 
connection  terminals  are  properly 
supported to relieve tension. 

  Check  to  ensure  all  screw  terminals  on 

all  conductors  are  tight  (motor  circuit 
breakers  Q1  to  Q6,  mains  circuit 
breakers  F1  to  F3,  contactors  Q11  to 
Q16  and  Q20  to  Q21,  etc.)  Tighten  all 
loose conductors with a screwdriver.  

  Visually  inspect  the  connection  of 

individual cables to the terminal strip X1 
(spring  clips)  and  the  LOGO!  control 
system (screw terminals). 

  Inspect  all  screw  terminals  for  the 

protective  green  and  yellow  PE 
grounding  conductor  in  the  electrical 
box,  the  motor  section,  the  cooling  unit 
and  the  pressure  vessel.  Tighten  any 
loose terminals. 

  Inspect  the  connector  X50  (dryer  and 

cooler) and the pressure sensor (B1) (on 
the pressure vessel). 

18.5.  Air  pumps  intake  filter  set 

replacement 

     (Fig. 18) 

 

The 

filters 

installed 

in 

the 

compressor  air  pump  crankcases 
must  be  replaced  during  regular 
operation of the compressor. 

 

 
 

Содержание DK50 9x4VRT/M

Страница 1: ...DK50 9x4VRT M User manual EN...

Страница 2: ...October 2018 Z_2195 2018 Chap 3 pgs 5...

Страница 3: ...RT M EKOM spol s r o Priemyseln 5031 18 SK 921 01 Pie any Slovak Republic tel 421 33 7967255 fax 421 33 7967223 www ekom sk email ekom ekom sk DATE OF LAST REVISION 10 2018 NP DK50 9x4VRTM_ED EN 2_10...

Страница 4: ...EQUIPMENT FUNCTION 14 10 PNEUMATIC DIAGRAM 16 INSTALLATION 17 11 CONDITIONS FOR USE 17 12 PLACEMENT OF THE COMPRESSOR 18 13 PNEUMATIC CONNECTIONS 20 14 ELECTRICAL CONNECTIONS 21 OPERATION 25 15 INITIA...

Страница 5: ...ther filtration Any use of the product outside the framework of its intended use is considered improper use The manufacturer is not liable for any damages or injury resulting from misuse 3 CONTRAINDIC...

Страница 6: ...der authorized by the manufacturer the product is used pursuant to the user manual The user manual corresponds to the configuration of the product and its compliance with applicable safety and technic...

Страница 7: ...ion occurs During repairs and maintenance ensure that product is disconnected from the mains pressure is released from all lines Only the manufacturer or a qualified specialist trained by the manufact...

Страница 8: ...rking pressure bar 6 8 6 8 Safety valve bar 10 10 Noise level dB 85 74 Total weight of compressor net kg 747 817 Weight compressor module kg 540 610 Weight dryer module kg 80 80 Weight of air tank kg...

Страница 9: ...pressor module kg 540 610 Weight dryer module kg 85 74 Weight of air tank kg 127 127 Compressor dimensions total w x d x h mm 3800x705 x2100 3800x705 x2100 Dimensions compressor module w x d x h mm 18...

Страница 10: ...Correction factor for working pressure p bar 4 5 6 7 8 9 10 FC1 0 78 0 85 0 93 1 0 1 06 1 11 1 15 Correction factor for temperature of compressed air entering the dryer tinlet C 30 35 40 45 50 55 FC2...

Страница 11: ...2 1 3 C C C n skut C F F F Q Q F Qskut actual airflow Qn nominal dryer flow 1800lit min FC1 working pressure correction factor FC2 correction factor for air entering the dryer FC3 dew point correction...

Страница 12: ...ls a condensing dryer module with connection hoses air tank module DK50 9x4VRTS M compressor comprised of the following modules Fig 1b a compressor module with 9 compressor air pumps and controls alon...

Страница 13: ...h a set of filters if needed A pressure regulator may be added to the set of filters The set of filters is fully compatible with all compressors listed above If a higher level of air filtration is req...

Страница 14: ...ator and into the condensing dryer 9 This continues to lower the temperature of the air and produces more condensate The temperature then rises to reduce the relative humidity The clean dry air then p...

Страница 15: ...0 9x4VRT M 10 2018 NP DK50 9x4VRTM_ED EN 2_10 2018 15 Fig 3 Electrical box switchboard 3 Electrical box switchboard 16 Display 17 Alarm indicator 18 Start stop button 19 Main switch 20 Temperature sen...

Страница 16: ...VRTS M 1 Inlet filter 2 Compressor air pump 3 Compressor fan 4 Solenoid valve 5 Safety valve 6 Check valve 7 Pressure relief valve 8 Condensate separator 9 Dryer 10 Pressure sensor 11 Pressure gauge 1...

Страница 17: ...e safety of the operator and maintenance personnel Operating the equipment in areas in which flammable mixtures may be present such as in operating rooms coal storage areas etc is prohibited Flammable...

Страница 18: ...bly compressor dryer and air tank modules to remove all packaging and release the transport anchors from the pallet Anchors securing all modules to the pallet 12 1 Handling Use a fork lift truck or si...

Страница 19: ...n Fig 7 Remove the transport stabilizers from the air pumps Fig 8 Remove all stabilizers on the air pumps once the compressor assembly has been positioned and levelled at the site of final installatio...

Страница 20: ...2_10 2018 20 10 2018 Position the air tank at the site of installation and anchor it to the floor Fig 9 13 PNEUMATIC CONNECTIONS Compressor module dryer module connect the air tank with the provided h...

Страница 21: ...valid technical standards The product is delivered without a power cord Connect the compressor module to the dryer module using the W22 cable Fig 14 Connect the compressor module to sensor B1 located...

Страница 22: ...DK50 9x4VRT M NP DK50 9x4VRTM_ED EN 2_10 2018 22 10 2018 Fig 13 Fig 14 Fig 15 Cable bridge...

Страница 23: ...addresses specific or requested from the manufacturer before the compressor is shipped or configure the IP addresses specific or requested based on the manual see the service manual or via the compres...

Страница 24: ...ariables The second option for monitoring compressor parameters using selected memory variables is the LOGO Variable function Clicking on the LOGO Variable button shows the screen on the display that...

Страница 25: ...witches on when pressure in the air tank drops to the pressure switch s lower limit level The compressor automatically switches off after reaching the pressure switch s upper limit level 15 INITIAL ST...

Страница 26: ...hich the display returns to the start screen Note The START button is preset to RETENTIVITY ON which means that if the compressor has been activated once using the START button the system remembers th...

Страница 27: ...nformation are shown on the display Temperatures above the critical values are shown as alarms The control panel on the controller has four cursor buttons ESC and OK buttons and four function buttons...

Страница 28: ...y than maintenance service interval signals The maintenance service interval is measured from the first time the equipment is energised All alarms are accompanied by a blinking red P2 Alarm indicator...

Страница 29: ...rmally Note The internal temperature monitoring function is not included for unenclosed compressors The display shows the current temperature inside the enclosed compressor module The alarm clears whe...

Страница 30: ...N Data is recorded on a micro SD card in a slot in the base module See the illustration The figure shows the location of the micro SD card onto which alarms and operating events are logged Information...

Страница 31: ...no risk of any other material damages Air pump components head cylinder and pressure hose are very hot when the compressor is running and just after it shuts down do not touch these components Repair...

Страница 32: ...x x See the dryer manual on the CD user Check compressor fan operation x Visual check of rotation during air pump operation user Replace float in separator x x x 18 7 025200146 000 qualified professio...

Страница 33: ...x x x 18 qualified professional Check temperature sensor switching function x x x x x x 18 12 qualified professional Replacement of piston group with bearing 6 8bar x x 604031764 000 qualified profes...

Страница 34: ...r air pump for normal operation and noise levels Check the operation of fans Check the condition of filters Check the condition of the air pump itself contamination in the crankcase and play in the cr...

Страница 35: ...er of turns until the valve itself vents Let the safety valve vent for only a few seconds Rotate the screw back to the right clockwise to the stop and the valve must be closed 18 7 Float replacement B...

Страница 36: ...ers 3 Clean or wash the filter if heavily contaminated in a solution of soapy water and allow to dry completely Reinstall the filters once dry reverse the procedure to reassemble In Point A remove the...

Страница 37: ...ank from 0 to 7 bar The measured value must be less than the data provided in the Technical data table 18 10 Check operation of check valves Compressed air circuit Check for proper operation of the ch...

Страница 38: ...ator does not turn 18 12 Checking the operation of temperature sensor switching Fig 24 This check is conducted using the LOGO TDE display where the instantaneous temperature values are shown on the st...

Страница 39: ...exceeds its pre set value The pressure relief valve closes as the pressure drops Pressure in the compressed air circuit can only increase because of an increase in flow resistance in the compressed a...

Страница 40: ...tighten Check the main power connection replace if damaged Problem with electrical power source Main breaker is off Controller or expansion module malfunction Replace the malfunctioning controller or...

Страница 41: ...or operation at a pressure of around 0 7 bar for a period of at least 1 hour then check the dryness of the compressed air 20 REPAIR SERVICE Guaranteed and post guarantee repairs must be done by the ma...

Страница 42: ...DK50 9x4VRT M NP DK50 9x4VRTM_ED EN 2_10 2018 42 10 2018 ANNEX 22 MAPPING PARAMETERS...

Страница 43: ...DK50 9x4VRT M 10 2018 NP DK50 9x4VRTM_ED EN 2_10 2018 43...

Страница 44: ...lay panel alarms operation in alarm conditions Y N N C Installation connection to equipment Y C Product maintenance maintenance intervals maintenance procedure service intervals operating activities Y...

Страница 45: ...TM_ED EN 2_10 2018 45 06 2018 DK50 9x4VRT M EKOM spol s r o Priemyseln 5031 18 921 01 PIE ANY Slovak Republic tel 421 33 7967255 fax 421 33 7967223 e mail ekom ekom sk www ekom sk NP DK50 9x4VRTM_ED E...

Отзывы: