CLEARANCES TO COMBUSTIBLES
A combustible shelf may be fixed to the wall above the fire, providing that it complies with the dimensions
given below.
A non-combustible shelf may be fitted to within 10mm of the top edge of the fireframe.
Combustible materials, such as wood, may be fitted to within 100mm (4in) of either side of the frame of the
appliance, providing the forward projection does not exceed 100mm (4in).
Any combustible side walls must be at least 500mm to the side of the radiant heat source.
As with all heating appliances, any decorations, soft furnishings, and wall coverings (i.e. flock, blown vinyl
and embossed paper) positioned too close to the appliance may discolour or scorch.
VENTILATION
This appliance requires purpose provided ventilation of at least 8.75cm
2
.
The requirements of other
appliances operating in the same space or room, and the results of a spillage test must be taken into con-
sideration when assessing ventilation requirements, this will have been carried out by your CORGI registered
installer.
For Republic of Ireland, ventilation may be required, see IS 813, ICP3, IS 327, and any other rules in force.
FUEL BED LAYOUT
1. Place the ceramic burner pad onto the
top of the burner as shown, taking care to
ensure it is centralised and pushed fully
against the back location ledge. Check that
all of the holes in the burner top plate are
unobscured.
2. Place the matrix into position as shown.
Slide it back to the rearmost position and
centralise.
2
3.0
4.0
5.0
Maximum depth of shelf Minimum distance from finished hearth surface
to underside of shelf
100mm (4in)
745mm (29 1/4 in)
150mm (6in)
845mm (33 1/4 in)
203mm (8in)
895mm (35 1/4 in)
©
2009 Focal Point Fires plc.