3
!
!
!
When the device is installed in place, make sure that the
shield is in the correct position according to the required
area masking.
Installation
At this point it is recommended to carry out the commis
-
sioning of the device (see “Commissioning”), or at least
the download of the physical address, using the program-
ming button placed close to the bus connector; alternati-
vely, programming mode can be activated later when the
device is already installed by means of the EK-QR6-IR
remote controller. Fix the sensor body to the base pla-
te securely through its own mounting screws and finally
adjust the position of the sensor head.
Section of shield applied
Active range (h = 2.5m)
Angular section
-8.5° per section
A + B
Ø 10 m
A
Ø 14 m
None
Ø 32 m
Warning!
The electrical connection of the device
can be carried out only by qualified personnel. The
incorrect installation may result in electric shock
or fire. Before making the electrical connections,
make sure the power supply has been turned off.
Warning!
In order to supply the KNX bus lines
use only KNX bus power supplies (e.g. ekinex EK-
AB1- TP or EK-AG1-TP). The use of other power
supplies can compromise the communication and
damage the devices connected to the bus.
Warning!
The sensor is a low voltage circuit; ne-
ver connect it with the 230V line network. Do not
run the KNX wiring in the same conduit used by
line network wiring.
In order to apply the shield, first remove the decorative
bezel from the body. Insert the clip of the shield section on
the edge of the bezel, so that it extends below. Reapply
the bezel making the shield cover part of the lens; the
bezel secures the shield edge against the body.
The device has degree of protection IP55 (Wall mount) /
IP54 (Ceiling mount), and is therefore suitable for use in
an outdoor environment. During the fixing of the base pla
-
te, until the wiring is connected and possibly the sensor
is tested for accuracy and correct positioning, the device
can be temporarily mounted by locking it on the baseplate
through a plastic hook. Once all adjustments have been
made, the sensor can be eventually mounted on the base
plate. For application on inner or outer corners, a corner
mounting support is available as an accessory.
Installation procedure - Standard mount
Apply the device body to the base plate by means of the
support hook:
Mount the base plate on the wall / ceiling in the desired
position by means of the supplied screw anchors. Drive
the incoming bus cable through the rubber perforation ca-
ble guides and connect the device.
The sensor head can be adjusted up to 40° downward
and 90° upward, and rotated horizontally max. 90° in ei-
ther direction.