- 9 -
Possible problem areas and solutions
5. Possible problem areas and their solutions
Problem
Reason
Solution
LED of external unit does
not illuminate
Maybe the power connection
(clamp 3,4) and the data
connection (clamp 1,2) are
interchanged
Connect power supply to
clamp 3 and 4. Connect
RS-485 bus to clamp 1
and 2.
Communication between
PC-Software and terminals
does not work.
1.
IP address of converter is
not concordant with the
settings in ekey
®
TOCAnet Admin software
2.
A firewall is active, which
blocks the UDP-data
transfer on port 21580,
21581 and 21589
1.
Change IP-address
2.
Open the described
ports in the firewall
(for UDP
communication).
LED of external unit is
blinking green
Fingerprint sensor can not
be activated. Maybe the
sensor is defect.
Contact an authorized
ekey
®
TOCAnet specialist
dealer
After a positive fingerprint
match the internal unit’s
display shows message
„En“ but the relay is not
switching
Maybe the relay is defect
Contact an authorized
ekey
®
TOCAnet specialist
dealer
„Ready“ LED at LAN/RS-
485 converter is
illuminating red.
Data lines Rx and Tx are
connected in the wrong
order to the converter.
Interchange data lines
LED of external unit is
illuminating orange
although the software
configuration in “ekey
®
TOCAnet Admin” is done
correctly
Data lines Rx and Tx are
connected in the wrong
order to the outside unit.
Interchange data lines