REPAIRS 

    
    

 

1. 

Should an electrical component fail, consult the Factory Service Center to obtain the  

 

 

proper replacement part. 

 
 

 

 

2. 

If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration  

 

 

technician to correct the fault.  Contact the Factory Service Center prior to initiating  

 

 

this action.  

 

 

 

Any  competent  refrigeration  technician  will  be  able  to  service  the  equipment.    The 
following procedure must be used: 

 
 

 

a.  The source of the leak must be determined and corrected. 

 
 

 

b.  The machine should be thoroughly evacuated before recharging. 

 

 

 

 

c.  The unit must be recharged with refrigerant measured accurately by weight. 

 
 

 

d.  For  evacuation  and  recharging  of  the  machine,  use  the  crimped  and  brazed 

charging stub attached to the side of the refrigerant compressor. 

 

 

 

 

The charging stub should be crimped and rebrazed after servicing.  

N

EVER

 

allow 

permanent service valves to be fitted to any part of the circuit.  Service valves may 
leak causing further loss of refrigerant gas. 

 

 

 

 

3. 

The refrigerant compressor fitted to the dehumidifier is a durable unit that should give 
many  years  of  service.    Compressor  failure  can  result  from  the  machine  losing  its 
refrigerant  gas.    The  compressor  can  be  replaced  by  a  competent  refrigeration 
technician.   

 
 

 

Failure of the compressor can be confirmed by the following procedure: 

 
 

 

a.  Establish that power is present at the compressor terminals using a voltmeter. 

 

 

 

b.  With  the  power  disconnected,  check  the  continuity  of  the  internal  winding  by 

using  meter  across  the  compressor  terminals.    An  open  circuit  indicates  that  the 
compressor should be replaced. 

 

 

 

c.  Check that the compressor is not grounded by establishing that a circuit does not 

exist between the compressor terminals and the shell of the compressor. 

Содержание 1028225

Страница 1: ...PD120 OWNERS MANUAL Drawing No TPC368 Issue 6 Date 07 09 18 EBAC MODEL PD120 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Страница 2: ...s the moist air through the cold evaporator coil which cools the air below its dew point Moisture forms on the evaporator coil and is collected in the condensate tray which is equipped with a permanen...

Страница 3: ...TH EPTH EPTH 658mm W W W WEIGHT EIGHT EIGHT EIGHT 70 5Kg A A A AIR IR IR IRFLOW FLOW FLOW FLOW Low 450 M3 hr High 850 M3 hr H H H HORSEPOWER ORSEPOWER ORSEPOWER ORSEPOWER 1 5 P P P POWER OWER OWER OWE...

Страница 4: ...unit inlet and outlet must have a clearance of 0 5M from all adjacent surfaces and or structures Before connecting this unit to the relevant power supply the following must be carried out Selecting t...

Страница 5: ...running for 15 minutes E Observe the evaporator coils behind the filter on the air inlet end of the unit to confirm frost formation i If the air temperature is below 70 F an even coating of frost shou...

Страница 6: ...the fins Alternatively vacuum clean the coils WARNING DO NOT STEAM CLEAN REFRIGERATION COILS 2 Check that the fan is firmly secured to the motor shaft and that the fan rotates freely The fan motor is...

Страница 7: ...of the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak cau...

Страница 8: ...on 4 Check the wiring diagram to find fault and repair Little or no water extraction 1 Insufficient air flow 2 Compressor fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory...

Страница 9: ...azard This product contains fluorinated greenhouse gases covered by the Kyoto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products...

Страница 10: ...90 www eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www...

Отзывы: