PD120 OWNERS MANUAL 

Drawing No.  :-  TPC368 
Issue 

:-  6 

Date 

:-  07/09/18 

ROUTINE SERVICE 

    
    

WARNING:  

ENSURE  THAT  THE  POWER  CORD  TO  THE  MACHINE 

HAS  BEEN  DISCONNECTED  BEFORE  CARRYING  OUT 
ROUTINE  SERVICE.  THE  SERVICING  AND  REPAIR  OF 
THIS  UNIT  SHOULD  ONLY  BE  CARRIED  OUT  BY  A 
SUITABLY QUALIFIED PERSON

 

 
To  ensure  continued  full  efficiency  of  the  dehumidifier,  maintenance  procedures  should  be 
performed as follows: 
 

 

 

 

1. 

Clean the surface of the evaporator and condenser coils by blowing the dirt out from 
behind the fins with compressed air.  Hold the nozzle of the air hose away from the 
coil (approx 6”) to avoid damaging the fins.  Alternatively, vacuum clean the coils. 

 
 
 

WARNING:  

DO NOT STEAM CLEAN REFRIGERATION COILS. 

 

 

 

 
 

2. 

Check that the fan is firmly secured to the motor shaft and that the fan rotates freely.  

The fan motor is sealed for life and therefore does not need oiling.

 

 

 

3. 

To  check  the  refrigerant  charge,  run  the  unit  for  15  minutes  and  briefly  remove  the 
cover.    The  evaporator  coil  should  be  evenly  frost  coated  across  its  surface.    At 
temperatures above 70

°

F, the coil may be covered with droplets of water rather than 

frost.    Partial  frosting  accompanied  by  frosting  of  the  thin  capillary  tubes,  indicates 
loss of refrigerant gas or low charge.  

 
 

4. 

Check all wiring connections. 

 

 

 
 

I

F ANY OF THE PRECEDING PROBLEMS OCCUR

,

 CONTACT THE 

E

BAC 

S

ERVICE 

C

ENTER PRIOR TO 

CONTINUED OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE

Содержание 1028225

Страница 1: ...PD120 OWNERS MANUAL Drawing No TPC368 Issue 6 Date 07 09 18 EBAC MODEL PD120 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Страница 2: ...s the moist air through the cold evaporator coil which cools the air below its dew point Moisture forms on the evaporator coil and is collected in the condensate tray which is equipped with a permanen...

Страница 3: ...TH EPTH EPTH 658mm W W W WEIGHT EIGHT EIGHT EIGHT 70 5Kg A A A AIR IR IR IRFLOW FLOW FLOW FLOW Low 450 M3 hr High 850 M3 hr H H H HORSEPOWER ORSEPOWER ORSEPOWER ORSEPOWER 1 5 P P P POWER OWER OWER OWE...

Страница 4: ...unit inlet and outlet must have a clearance of 0 5M from all adjacent surfaces and or structures Before connecting this unit to the relevant power supply the following must be carried out Selecting t...

Страница 5: ...running for 15 minutes E Observe the evaporator coils behind the filter on the air inlet end of the unit to confirm frost formation i If the air temperature is below 70 F an even coating of frost shou...

Страница 6: ...the fins Alternatively vacuum clean the coils WARNING DO NOT STEAM CLEAN REFRIGERATION COILS 2 Check that the fan is firmly secured to the motor shaft and that the fan rotates freely The fan motor is...

Страница 7: ...of the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak cau...

Страница 8: ...on 4 Check the wiring diagram to find fault and repair Little or no water extraction 1 Insufficient air flow 2 Compressor fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory...

Страница 9: ...azard This product contains fluorinated greenhouse gases covered by the Kyoto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products...

Страница 10: ...90 www eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www...

Отзывы: