TROUBLESHOOTING 

S

YMPTOM

 

C

AUSE

 

R

EMEDY

 

Unit inoperative 

1.  No power to unit 

1.  Check the power from 
power supply panel 

Little or no airflow 

1. Fan motor burnt out 
2. Dirty refrigeration coils 
3. Loose electrical wiring 

1. Replace the fan motor 
2. See 

Routine Maintenance

  

Section 
3. Check the wiring diagram 
to find fault and repair 

Little or no water 
extraction 

1. Insufficient air flow 
2. Compressor fault 
3. Loss of refrigerant gas 

1. Check all of the above 
2. Contact the Factory 
Service Center 
3. Contact the Factory 
Service Center 

Little or no defrost 
when required 

1. Faulty timer 
2. Faulty by-pass valve 

1. Contact the Factory 
Service Center 
2. Contact the Factory 
Service Center 

Unit vibrates 
excessively 

1. Loose compressor 
2. Damaged fan 

1. Tighten the nuts on the 
compressor mounts 
2. Replace fan 

Water flooding inside 
the machine 

1. Drain pipe blocked/frozen 
2. Drain pipe too high 
3. Crimped or blocked tubing 

1. Clear the obstruction 
2. Ensure that no section of 
the drain hose is 1M max. 
above the level of the water 
outlet 
3. Straighten, clear, or replace 
tubing 

 

Содержание ECO85

Страница 1: ...Limited Unit 5a Commercial Yard Settle North Yorkshire BD24 9RH Get In Touch Call 0845 6880112 Email info adremit co uk Page 1 of 12 Drawing TPC390 Issue 5 Date 17 01 17 ECO85 INDUSTRIAL DEHUMIDIFIER...

Страница 2: ...y removed during the cooling phase plus the additional heat generated by the compressor The air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute hum...

Страница 3: ...he refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For ty...

Страница 4: ...h the evaporator filter panel i If the air temperature is below 80 F an even coating of frost should cover the entire evaporator coil ii If the air temperature is above 80 F frost and or droplets of c...

Страница 5: ...ator coil should be evenly frost coated across its surface At temperatures above 80 F the coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the t...

Страница 6: ...machine use the crimped and brazed charging stub attached to the side of the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valv...

Страница 7: ...ittle or no water extraction 1 Insufficient air flow 2 Compressor fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Lit...

Страница 8: ...ry Tube 3014254 2 x 24 4 Solenoid Valve 3020837 1 5 Filter Dryer 3020909 1 6 Compressor 3944932 1 7 Solenoid Coil 3030451 1 8 Run Capacitor 3030908 1 9 Filter 2029826 1 10 Mains Lead 3031231 1 11 Fan...

Страница 9: ...azard This product contains fluorinated greenhouse gases covered by the Kyoto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products...

Страница 10: ...Our Address Puravent Adremit Limited Unit 5a Commercial Yard Settle North Yorkshire BD24 9RH Get In Touch Call 0845 6880112 Email info adremit co uk Page 10 of 12 Drawing TPC390 Issue 5 Date 17 01 17...

Страница 11: ...Our Address Puravent Adremit Limited Unit 5a Commercial Yard Settle North Yorkshire BD24 9RH Get In Touch Call 0845 6880112 Email info adremit co uk Page 11 of 12 Drawing TPC390 Issue 5 Date 17 01 17...

Страница 12: ...uckland County Durham DL14 9AD Tel 44 0 1388 664400 Fax 44 0 1388 662590 www eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport Ne...

Отзывы: