REPAIRS 

 

 

1. 

Should  an  electrical  component  fail,  consult  the  Factory  Service 
Center to obtain the proper replacement part. 

 

 

 

2. 

If refrigerant gas is lost from the machine, it will be necessary to use 
a  refrigeration  technician  to  correct  the  fault.    Contact  the  Factory 
Service Center prior to initiating this action.  

 

 

 

Any  competent  refrigeration  technician  will  be  able  to  service  the 
equipment.  The following procedure must be used: 

 
 

 

a.  The source of the leak must be determined and corrected. 

 
 

 

b.  The  machine  should  be  thoroughly  evacuated  before 

recharging. 

 

 

 

 

c.  The  unit  must  be  recharged  with  refrigerant  measured 

accurately by weight. 

 
 

 

d.  For evacuation and recharging of the machine, use the crimped 

and brazed charging stub attached to the side of the refrigerant 
compressor. 

 

 

 

 

The  charging  stub  should  be  crimped  and  rebrazed  after 
servicing.  

N

EVER

 

allow permanent service valves to be fitted to 

any part of the circuit.  Service valves may leak causing further 
loss of refrigerant gas. 

 

 

 

3. 

The  refrigerant  compressor  fitted  to  the  dehumidifier  is  a  durable 
unit that should give many years of service.  Compressor failure can 
result from the machine losing its refrigerant gas.  The compressor 
can be replaced by a competent refrigeration technician.   

 
 

 

Failure  of  the  compressor  can  be  confirmed  by  the  following 
procedure: 

 
 

 

a.  Establish  that  power  is  present  at  the  compressor  terminals 

using a voltmeter. 

 

 

 

b.  With the power disconnected, check the continuity of the internal 

winding  by  using  meter  across  the  compressor  terminals.    An 
open circuit indicates that the compressor should be replaced. 

 

 

 

c.  Check that the compressor is not grounded by establishing that 

a  circuit  does  not  exist  between  the  compressor  terminals  and 
the shell of the compressor.     

Содержание ECO85

Страница 1: ...Limited Unit 5a Commercial Yard Settle North Yorkshire BD24 9RH Get In Touch Call 0845 6880112 Email info adremit co uk Page 1 of 12 Drawing TPC390 Issue 5 Date 17 01 17 ECO85 INDUSTRIAL DEHUMIDIFIER...

Страница 2: ...y removed during the cooling phase plus the additional heat generated by the compressor The air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute hum...

Страница 3: ...he refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For ty...

Страница 4: ...h the evaporator filter panel i If the air temperature is below 80 F an even coating of frost should cover the entire evaporator coil ii If the air temperature is above 80 F frost and or droplets of c...

Страница 5: ...ator coil should be evenly frost coated across its surface At temperatures above 80 F the coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the t...

Страница 6: ...machine use the crimped and brazed charging stub attached to the side of the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valv...

Страница 7: ...ittle or no water extraction 1 Insufficient air flow 2 Compressor fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Lit...

Страница 8: ...ry Tube 3014254 2 x 24 4 Solenoid Valve 3020837 1 5 Filter Dryer 3020909 1 6 Compressor 3944932 1 7 Solenoid Coil 3030451 1 8 Run Capacitor 3030908 1 9 Filter 2029826 1 10 Mains Lead 3031231 1 11 Fan...

Страница 9: ...azard This product contains fluorinated greenhouse gases covered by the Kyoto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products...

Страница 10: ...Our Address Puravent Adremit Limited Unit 5a Commercial Yard Settle North Yorkshire BD24 9RH Get In Touch Call 0845 6880112 Email info adremit co uk Page 10 of 12 Drawing TPC390 Issue 5 Date 17 01 17...

Страница 11: ...Our Address Puravent Adremit Limited Unit 5a Commercial Yard Settle North Yorkshire BD24 9RH Get In Touch Call 0845 6880112 Email info adremit co uk Page 11 of 12 Drawing TPC390 Issue 5 Date 17 01 17...

Страница 12: ...uckland County Durham DL14 9AD Tel 44 0 1388 664400 Fax 44 0 1388 662590 www eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport Ne...

Отзывы: