Drawing   : - TPC390 
Issue 

: - 5 

Date 

: - 17/01/17 

 

 

ROUTINE SERVICE 

 

 
 
 
 
 
 
 
To  ensure  continued  full  efficiency  of  the  dehumidifier,  maintenance 
procedures should be performed as follows: 
 

 

 

 

1. 

Clean the surface of the evaporator and condenser coils by blowing 
the  dirt  out  from  behind  the  fins  with  compressed  air.    Hold  the 
nozzle of the air hose away from the coil to avoid damaging the fins.  
Alternatively, vacuum clean the coils. 

 

 
 
 
 

 
 

2. 

Check that the fan is firmly secured to the motor shaft and that the 
fan rotates freely.  

The fan motor is sealed for life and therefore 

does not need oiling.

 

 

 

3. 

To  check  the  refrigerant  charge,  run  the  unit  for  15  minutes  and 
briefly  remove  the  evaporator  filter  cover.    The  evaporator  coil 
should  be  evenly  frost  coated  across  its  surface.    At  temperatures 
above  80

°

F,  the  coil  may  be  covered  with  droplets  of  water  rather 

than  frost.    Partial  frosting  accompanied  by  frosting  of  the  thin 
capillary tubes, indicates loss of refrigerant gas or low charge. 

 
 

4. 

Check all wiring connections. 

  

 

To  check  the  operation  of  the  defrost  system,  switch  the  machine 
on and leave it running for approximately 55 minutes.  The machine 
will then enter “Hot Gas” defrost mode for approximately 5 minutes 
before returning to normal operation.  If the unit will not defrost, the 
printed  circuit  timer  board  may  be  defective  or  the  by-pass  valve 
may be inoperable.  

 
 

I

F ANY OF THE PRECEDING PROBLEMS OCCUR

,

 CONTACT THE 

E

BAC 

S

ERVICE 

C

ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO 

PREVENT PERMANENT DAMAGE

.

   

 

WARNING: 

ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN 

DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE. 
THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE 

CARRIED OUT BY A SUITABLY QUALIFIED PERSON. 

WARNING:

 

DO NOT STEAM CLEAN REFRIGERATION COILS 

Содержание ECO85

Страница 1: ...Limited Unit 5a Commercial Yard Settle North Yorkshire BD24 9RH Get In Touch Call 0845 6880112 Email info adremit co uk Page 1 of 12 Drawing TPC390 Issue 5 Date 17 01 17 ECO85 INDUSTRIAL DEHUMIDIFIER...

Страница 2: ...y removed during the cooling phase plus the additional heat generated by the compressor The air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute hum...

Страница 3: ...he refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For ty...

Страница 4: ...h the evaporator filter panel i If the air temperature is below 80 F an even coating of frost should cover the entire evaporator coil ii If the air temperature is above 80 F frost and or droplets of c...

Страница 5: ...ator coil should be evenly frost coated across its surface At temperatures above 80 F the coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the t...

Страница 6: ...machine use the crimped and brazed charging stub attached to the side of the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valv...

Страница 7: ...ittle or no water extraction 1 Insufficient air flow 2 Compressor fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Lit...

Страница 8: ...ry Tube 3014254 2 x 24 4 Solenoid Valve 3020837 1 5 Filter Dryer 3020909 1 6 Compressor 3944932 1 7 Solenoid Coil 3030451 1 8 Run Capacitor 3030908 1 9 Filter 2029826 1 10 Mains Lead 3031231 1 11 Fan...

Страница 9: ...azard This product contains fluorinated greenhouse gases covered by the Kyoto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products...

Страница 10: ...Our Address Puravent Adremit Limited Unit 5a Commercial Yard Settle North Yorkshire BD24 9RH Get In Touch Call 0845 6880112 Email info adremit co uk Page 10 of 12 Drawing TPC390 Issue 5 Date 17 01 17...

Страница 11: ...Our Address Puravent Adremit Limited Unit 5a Commercial Yard Settle North Yorkshire BD24 9RH Get In Touch Call 0845 6880112 Email info adremit co uk Page 11 of 12 Drawing TPC390 Issue 5 Date 17 01 17...

Страница 12: ...uckland County Durham DL14 9AD Tel 44 0 1388 664400 Fax 44 0 1388 662590 www eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport Ne...

Отзывы: