6. Troubleshooting
TEC 2000 Installation & Operation Manual E2K-405-0902
6-1
6
Troubleshooting
X
CAUTION:
This actuator is non-intrusive. Do not open the control compartment on the
actuator unless absoutely necessary. It was sealed in dry-clean conditions in the factory
and entry into this compartment should not be necessary. Unauthorized entry could void
the warranty.
6.1. Troubleshooting Problems/Corrective Action for Actuator
Operation
Symptom
Probable Cause
Corrective Action
Blown Control Fuse
Check fuse and replace as necessary.
Open in Control Circuit
Refer to appropriate wiring diagram and check
for continuity
Motor will not Run
Insulation Resistance
Breakdown in Motor
Perform Megger Test
No power available
to actuator
Tripped circuit breaker
Reset circuit breaker
Valve stem improperly
lubricated
Clean out old grease and replace with
recommended lubricant
Actuator lubrication has broken
down
Clean out old grease and replace with
recommended lubricant
Valve packing gland too tight
Loosen packing gland nuts as necessary
Drive sleeve bearing failure
Replace Bearing
Handwheel hard to
turn
Jammed valve
Refer to valve maintenance
Torque switch setting too low
Check setting and reset if necessary
Valve only opens or
closes partially with
motor
Limit switch improperly set
Check switch actuation and recalibrate if
necessary
Damaged or bent valve stem
Refer to valve maintenance
Valve packing too tight
Refer to valve maintenance
Torque switch is
properly set, but
actuator Torque’s
out in mid-travel,
open or closed
direction
Jammed valve (obstruction in
line)
Refer to valve maintenance