5. Customizing Actuator Settings
TEC 2000 Installation & Operation Manual E2K-405-0902
5-16
Table 5-2 Relay Outputs #1 through #5 Configuration
Relay
Default
Function
Configurable
Function
Configure
N.O./N.C.
Default
Setting
Configure
Flashing
RO#1
LSO
Valve full OPEN
See
Table 5-3
Relay Output
Function List
Yes
N.O.
Yes
RO#2
LSC
Valve full
CLOSE
See
Table 5-3
Relay Output
Function List
Yes
N.O.
Yes
RO#3
LSA
Intermediate
limit in closing
direction
See
Table 5-3
Relay Output
Function List
Yes
N.O.
Yes
RO#4
LSB
Intermediate
limit in opening
direction
See
Table 5-3
Relay Output
Function List
Yes
N.O.
Yes
RO#5
Monitor
Valve not
available
Generic – see
NOTE
No
1 N.O.
and
1 N.C.
Yes
NOTE: Generic means the control of this relay has been given to the network if a Controlinc
card has been installed. The relay will
not
function if the Controlinc card is not installed.
Flashing means the output will cycle ON and OFF in one second intervals while the function
is active.