5. Customizing Actuator Settings
TEC 2000 Installation & Operation Manual E2K-405-0902
5-26
Figure 5-14-1 Network Setup
NO
YES
NO
YES
NO
YES
YES
NO
NOTE: The actuator senses that the Controlinc ACM is installed and adjusts
the display sequence to display only one output
CALIBRATE
AIN#1 4-20MA?
CALIBRATE
4MA?
4MA
REFERENCE
APPLIED?
ACCEPT 4MA
SETTING?
See Figure 5-14-2
NO
YES
NO
YES
YES
NO
CALIBRATE
20MA?
20MA
REFERENCE
APPLIED?
ACCEPT
20MA
SETTING?
NO
YES
NO
YES
NO
YES
YES
NO
CALIBRATE
AIN#2 4-20MA?
CALIBRATE
4MA?
4MA
REFERENCE
APPLIED?
ACCEPT 4MA
SETTING?
NO
YES
NO
YES
YES
NO
CALIBRATE
20MA?
20MA
REFERENCE
APPLIED?
ACCEPT
20MA
SETTING?
NETWORK
SETUP?
NETWORK
NODE
ADDRESS 001
NO
YES
YES
NO
Goto next display
see Figure 5-4
001-254
REPONSE
DELAY 008
MS
NO
YES
001-255 mS
1 mS increments
PARITY
NONE
NO
YES
EVEN
ODD
NONE
ANALOG I/O
SCALE 0-100
NO
YES
0-100
0-1000
0-4095
Содержание TEC2000