5. Customizing Actuator Settings
TEC 2000 Installation & Operation Manual E2K-405-0902
5-27
Figure 5-14-2 – Network Setup Continued
NO
YES
NO
YES
NO
YES
YES
NO
NO
YES
NO
YES
YES
NO
NO
YES
NO
YES
CALIBRATE
AO#1 4-20MA?
CALIBRATE
4MA?
CALIBRATE
20MA?
IS EXTERNAL
METER
CONNECTED?
IS EXTERNAL
METER
CONNECTED?
ACCEPT 4MA
SETTING?
INCREASE
SETTING
0.005MA?
DECREASE
SETTING
0.005MA?
ACCEPT 20MA
SETTING?
NO
YES
NO
YES
INCREASE
SETTING
0.005MA?
DECREASE
SETTING
0.005MA?
From last display in
Figure 5-14-1
Return to
NETWORK SETUP?
in Figure 5-14-1.
5.6.10. Tag Name Setup
1. At the “
TAG NAME SETUP?
” prompt, answer, “
YES
.”
2. Use the control knob (
NO
) to increment the data entry selection for each character.
NOTE: The tag name consists of a maximum of sixteen characters. Spaces and dashes
are included in the sequence of “space,” “-,“ “0-9,” “A-Z.”
3. At the “
ACCEPT?
” prompt, answer, “
YES
” for each character.
4. Use the selector knob (
BACK
) to make changes to the previous characters in the tag
name while entering the data.