Chapter 15: Configuring Modbus/TCP
egnite Querx supports data transfer via Modbus/TCP, which can be used to
integrate the device into industrial process monitoring systems (SCADA).
Activating Modbus/TCP
Open the configuration page
Interfaces / Modbus
.
1.
Enable
Modbus/TCP.
2.
If you want to permit changes to the Modbus/TCP configuration, deactivate the
Write protection
checkbox.
3.
Click
Save
to apply your changes.
Modbus Register
Read Register
Address
Offset
Format
Contents
30010
9
int16
Error bits
0x0001: Temperature sensor error
0x0002: Humidity sensor error
0x0004: Dew-point error
0x0008: Air pressure sensor error
0x8000: Battery flat
30011
10
int16
Temperature Centigrade * 10
30012
11
int16
Relative humidity %
30013
12
int16
Temperature Fahrenheit * 10
30014
13
int16
Temperature Kelvin * 10
30015
14
int16
Dew-point Centigrade * 10
30016
15
int16
Dew-point Fahrenheit * 10
30017
16
int16
Dew-point Kelvin * 10
30019
18
int16
Absolute air pressure in hPa * 10
30020
19
int16
Relative air pressure in hPa * 10