background image

18.

It allows to adjust the balancing of the two airflows. 

Press OK to enter. 

Select the submenu item using 

 or 

: press OK to confirm.

1 Advanced Balancing

It allows to set the airflow balancing at speed 1-2-3-Boost, in supply and extract, only if the unit 

operates in Normal Mode 3V.

Choose NO or YES using 

 or 

Press OK to confirm.

Factory setting (DEFAULT): NO

If “NO”, the submenu “2 Supply Airflow” is displayed.

It allows to adjust the supply airflow against the extract airflow: the selected value is applied to 

any speed.

The setting range is: -30% ÷ +30%.

Factory setting (DEFAULT): 0%.

Increase/decrease the speed using 

 or 

Press OK to select.

Press ESC to go back to the previous menu.

If “YES”, new submenu items are displayed which allows to set the airflow balancing for each 

speed (1-2-3-Boost) and for each motor (supply/extract).

The setting range for any speed is: -30% ÷ +30%.

Factory setting for any speed (DEFAULT): 0%.

Increase/decrease the speed using 

 or 

Press OK to select.

Press ESC to go back to the previous menu.

Installer Menu

8 Heating
10 Speed setting 
11 Airflow Balancing
12 F7 filter 
13 Filter Alarm interval

It allows to select the F7 filter in case the unit is not equipped with it from factory.

The F7 filter should be installed to the “supply air side T22” (Fig. 7.a).

Press OK to enter.

Choose NO or YES using 

 or 

.

Press OK to select.

Factory setting (DEFAULT): Yes.

Installer Menu

8 Heating
10 Speed setting 
11 Airflow Balancing
12 F7 filter 
13 Filter Alarm interval

It allows to set the Filter Alarm period: the system has a timer which activates the Filter warning (Fig. 

7.b -      ) on the LCD at regular intervals. 

Press OK to enter. 

Choose among 2-3-4-5-6 months using 

 or 

.

Press OK to select. 

Factory setting (DEFAULT): 3 months

Installer Menu

8 Heating
10 Speed setting 
11 Airflow Balancing
12 F7 filter 
13 Filter Alarm interval

e

Currently not available.

Installer Menu

15 Constant Pressure
17 Periodic purge
18 Working Hours Counter
19 ModBus settings
20 Save settings

Содержание Homevent VIGO 550A

Страница 1: ...wn special duct If the environment in which the product is installed also houses a fuel operating device water heater methane stove etc that is not a sealed chamber type it is essential to ensure adeq...

Страница 2: ...interruption to the unit any period more than 72 hours can create a health and safety hazard damage components and will invalidate any warranty Operating temperature 0 C up to 40 C Service Although th...

Страница 3: ...INEARE BORDI NETTI NOME FIRMA SE NON SPECIFICATO QUOTE IN MILLIMETRI FINITURA SUPERFICIE TOLLERANZE INTERRUZIONE QR Fig 3 a Connections in LEFT and RIGHT orientation A B C D E F LEFT A Intake air from...

Страница 4: ...understood and applied The appliance is delivered in one carton box The appliance should be stored and transported in such a way that it is protected against physical damage that can harm spigots casi...

Страница 5: ...flat surface wall The unit must always be installed vertically It s important that the unit is completely leveled before it is put into operation Place the unit preferably in a separate room e g stora...

Страница 6: ...the back of the unit 5 c Hook the unit at its bracket 5 d Make sure it is at spirit level and fix it by means of the safety screw 5 e Connect the condensation drain joints G 3 4 M placed in the botto...

Страница 7: ...t must be earthed The units are wired internally from factory To connect the the CTRL DSP to the mother board use a 4 poles twisted pair cable 30m max length Unit comes pre wired with mains supply cab...

Страница 8: ...unit is disconnected before performing any installation service maintenance or electrical work WARNING The installation and service of the unit and complete ventilation system must be performed by an...

Страница 9: ...of a high efficiency level as well as of the humidity rate Table 6 c indicates the sound level at the different speeds Static Pressure Pa Airflow m3 h 0 50 100 150 200 250 300 350 400 450 500 550 600...

Страница 10: ...14 10 80 20 50 96 3 0 39 93 5 0 74 91 1 1 07 88 9 1 39 86 9 1 67 0 50 20 30 94 2 0 02 89 3 0 85 1 0 81 5 0 78 2 0 0 60 20 40 95 0 11 91 0 18 87 3 0 23 83 8 0 24 80 4 0 23 0 70 20 50 95 8 0 2 92 5 0 3...

Страница 11: ...78 47 Exhaust 78 65 70 71 62 59 53 45 80 50 Breakout 81 69 67 69 62 56 48 36 82 48 Speed 80 Lw dB SOUND POWER OCTAVE BAND Lp dB A 63 125 250 500 1 K 2 K 4 K 8K Tot 3m Intake 73 61 67 69 59 56 50 43 75...

Страница 12: ...that BOOST speed is activated DISABLED shows that the CTRL DSP is disabled BOOST to manually activate the BOOST speed to move to the right when setting the Weekly Timer FILTRO to reset the Filter Ala...

Страница 13: ...anually changed using or In case the IAQ sensor input is activated as per Fig 5h e g HY or IAQ sensor the unit speed increases by 15 and the icon is displayed Once the IAQ input is deactivated the uni...

Страница 14: ...enu 1 Mode Selection 2 Boost 3 Boost Duration 4 Reset FILTER Alarm 5 Night Mode 6 Weekly timer 7 Installer Menu It allows to reset the Filter Alarm after maintenance replacement only when FILTER is di...

Страница 15: ...layed Change the days using or Press OK to set the daily time program max 4 time slots Switch from hours minutes speeds using or Change hours minutes speeds using or The daily program can be copied in...

Страница 16: ...ULT Left Installer Menu 1 Language 2 Date time 3 Machine orientation 4 Normal Mode 6 Bypass settings It allows to select the orientation of the duct connections from and to outside LEFT or RIGHT hand...

Страница 17: ...t or Holiday Press OK to enter Choose speed 1 speed 2 speed 3 Boost or Holiday using or Press OK to select The setting ranges are Speed 1 10 80 Factory setting DEFAULT 40 Speed 2 20 90 Factory setting...

Страница 18: ...any speed DEFAULT 0 Increase decrease the speed using or Press OK to select Press ESC to go back to the previous menu Installer Menu 8 Heating 10 Speed setting 11 Airflow Balancing 12 F7 filter 13 Fi...

Страница 19: ...Weekly Timer is OFF Press OK to enter Press ESC to go back to the previous menu Installer Menu 15 Constant Pressure 17 Periodic purge 18 Working Hours Counter 19 ModBus settings 20 Save settings The u...

Страница 20: ...he indoor and outdoor temperature combinations are such that the heat exchange is not recommended If activated the Bypass icon is displayed Fig 7 b ANTI FROST Intake fan speed is reduced during very c...

Страница 21: ...11 11 10 10 9 9 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 N DISEGNO SCALA 1 1 TITOLO MATERIALE DATA DISEG VERIF APPR FABB Qual ANGOLARE FINITURA LINEARE BORDI NETTI NOME FIRMA SE NON SPECIFICATO QUOTE IN MILLI...

Страница 22: ...form this operation may vary depending on indoor and outdoor ambient conditions Press FILTER button Fig 7 b to reset the Filter Alarm Filters must be replaced every year MAINTENANCE WARNING Make sure...

Страница 23: ...epending on indoor and outdoor ambient conditions and on frequency of filter cleaning Clean the fans every year with a vacuum cleaner following the below illustrations Fig 8 f g k The actual need to p...

Страница 24: ...Unpleasant smell 1 Drain connections have not been installed correctly 2 Drain connection below the unit has a too low water level fill it up with water 3 Check filters Change of filters required 4 Ch...

Страница 25: ...y instructions www homevent co uk t Airflow sensitivity to pressure variations N A u Indoor outdoor air tightness m3 h N A v1 AEC Annual electricity consumption warm climates kWh 2 2 3 7 5 2 v2 AEC An...

Страница 26: ...26 NOTES...

Страница 27: ...27 NOTES...

Страница 28: ...Tel 44 0 1384 275822 Email sales homevent co uk 46 Third Avenue Pensnett Trading Estate Kingswinford West Midlands DY6 7US UK www homevent co uk VIGO 550A ISSUE A 03 21...

Отзывы: