8 / 10
P/N 3100010-
EN • REV 09 • ISS 14JAN15
Specifications
Voltage
Refer to Table
2
and Table
3
Current
Refer to
Table
2
and Table
3
Dimensions
Refer
to Table
4
Weight
Tone Generator
Speaker/Amp
6 lb. (2.7 kg)
9 lb. (4.1 kg)
Hazardous locations
Ambient
temp.
−31 to 104°F (−35 to +40°C)
Nonhazardous locations
Variable ambient temp.
−40 to 151°F (−40 to +66°C)
Table 1: Operating temperature codes
Model
number
Supply
wire
Class I, Div. 2
Groups A, B, C, D
Class II, Div. 2,
Groups F, G
Class III, Div. 1, 2
5532M
-
AQ
5532M
-
N5
5532MHV
-
AQ
5540M
-
24AQ
5540M
-
24N5
5540MV
-
24N5
5540M
-
120N5*
75°C
160°C (T3C)
160°C (T3C)
18
0°C (T3A)
1
35°C (T4)
1
35°C (T4)
1
35°C (T4)
1
35°C (T4)
100°C (T5)
5532M
-Y6
5532MHV
-Y6
5540M
-
24Y6
5540MV
-
24Y6
5540M
-
120Y6*
75°C
160°C (T3C)
18
0°C (T3A)
1
35°C (T4)
1
35°C (T4)
1
35°C (T4)
100°C (T5)
Table 2: Input board
Model number
Voltage
Current
5540M
-
24AQ
5540M
-
24N5
5540MV
-
24N5
5540M
-
24Y6
5540MV
-
24Y6
24 VDC
6 mA
5540M
-
120N5
5540M
-
120Y6
120V 50/60 Hz
13 mA
Table 3: Main power
Model number
Voltage
Standby
current
Tone on
current
Tone generator
5540M
-
24AQ
24 VDC
24 VAC 50/60 Hz
0.10 A
0.10 A
0.74 A
1.3 A
5540M
-
24N5
5540MV
-
24N5
120 VAC 50/60 Hz
0.10 A
0.36 A
5540M
-
24Y6
5540MV
-
24Y6
125 VDC
250 VDC
120 VAC 50/60 Hz
240 VAC
50/60 Hz
0.10 A
0.02 A
0.10 A
0.10 A
0.21 A
0.10 A
0.32 A
0.20 A
5540M
-
120N5
120 VAC 50/60 Hz
0.10
0.38 A
5540M
-
120Y6
125 VDC
250 VDC
120 VAC 50/60 Hz
240 VAC 50/60 Hz
0.10 A
0.02 A
0.10 A
0.10 A
0.20 A
0.10 A
0.31 A
0.20 A
Speaker/Amplifier at standard volume
5532M
-
AQ
24 VDC
24 VAC 50/60 Hz
0.10 A
0.10 A
0.74 A
1.3 A
5532M
-
N5
120 VAC 50/60 Hz
0.10 A
0.36 A
Model number
Voltage
Standby
current
Tone on
current
5532M
-Y6*
125 VDC
250 VDC
120 VAC 50/60 Hz
240 VAC
50/60 Hz
0.10 A
0.02 A
0.10 A
0.10 A
0.21 A
0.10 A
0.32 A
0.20 A
5532B
-
AQ
24 VDC
36 VDC
24 VAC 60 Hz
24 VAC 50 Hz
0.06 A
0.07 A
0.26 A
0.26 A
0.69 A
0.84 A
1.36 A
1.36 A
5532B
-
N5
120 VAC 60 Hz
120 VAC 50 Hz
0.10 A
0.09 A
0.29 A
0.29 A
5532B
-Y6
125 VDC
250 VDC
120 VAC 60 Hz
240 VAC 60 Hz
120 VAC 50 Hz
240 VAC 50 Hz
0.05 A
0.04 A
0.10 A
0.11 A
0.09 A
0.10 A
0.16 A
0.10 A
0.29 A
0.23 A
0.29 A
0.22 A
Speaker/Amplifier at high volume
5532MHV
-
AQ
24 VDC
24 VAC 50/60 Hz
0.10 A
0.10 A
1.5 A
2.3 A
5532MHV
-Y6
125 VDC
250 VDC
120 VAC 50/60 Hz
240 VAC 50/60 Hz
0.10 A
0.02 A
0.10 A
0.10 A
0.39 A
0.19 A
0.56 A
0.34 A
5532BHV
-
AQ
24 VDC
36 VDC
24 VAC 60 Hz
24 VAC 50 Hz
0.06 A
0.07 A
0.26 A
0.26 A
1.51 A
1.98 A
1.86 A
1.86 A
5532BHV
-Y6
125 VDC
250 VDC
120 VAC 60 Hz
240 VAC 60 Hz
120 VAC 50 Hz
240 VAC 50 Hz
0.05 A
0.04 A
0.10 A
0.11 A
0.09 A
0.10 A
0.25 A
0.23 A
0.62 A
0.33 A
0.62 A
0.33 A
*5532M
-
Y6 is suitable for use with 120 / 240 VAC main power input in
conjunction with the 5541M
-
Y6 Millennium System Master either for
emergency / evacuation, non
-
fire, or for supplementary fire alarm
control panel accessory applications. See the installation and operation
instructions for the 5541M
-Y6 (P/N
3100471).
Table 4: Speaker/Amplifier dimensions
5531M
5531MHV
A
8-
7/8 in. (225 mm)
11-
1/2 in. (292 mm)
B
8-
1/4 in. (210 mm)
9
-
3/4 in. (248 mm)
C
13 in. (330 mm)
14
-
1/4 in. (362 mm)
A
B
C